4. Programmable Register Overview
All M2110P Smart Pressure Gauges have programmable registers that allow the gauge to be configured to fit
the pressure measurement application. Programmable registers are numbered P0 through P8. Each register
controls a specific aspect of the gauge’s performance.
A description of all programmable registers, and step by step instructions for their use, is included below. Each
register is found on all M2110 series models, and performs the same function described for all models, except
as noted otherwise.
Px
Name
Description
Value Range
Notes
P0
Lockout Code
Lockout for security.
00 to 99
00 = Disabled.
P1
Timeout
Automatic shutoff in minutes of keypad
inactivity.
0 (disabled), 1, 2, 5,
10, 15, 25
Battery model only.
P2
Damp Rate
Exponential damping time in seconds.
0.1, 0.2, 0.5, 1, 2, 5,
10, 15, 25, 50
0.1 = No Damping.
P3
Density of Water
Reference
Temperature
Sets reference temperature for water
density when gauge is set for water
column units.
20°C, 4°C, or 60°F
P4
User Units
Full Scale
Enables gauge to display units other
than factory defined Engineering Units.
0 to 9,999 (Keypad)
0 to 19,999 (Serial)
User defined value.
SetPoint Model: defines which relay
outputs are active.
0 = Disabled.
1 = SET1 only.
2 = SET2 only.
3 = Both enabled.
P5
SetPoint Options
Current Loop Model: defines the status
of the 4 - 20 mA output.
0 = 4-20 disabled
1 = 4-20 enabled
Not found on
Battery model.
P6
SET1
Controls SET1 relay or 4.00 mA value.
–20% to +120% FS
User defined value.
P7
SET2
Controls SET2 relay or 20.0 mA value.
–20% to +120% FS
User defined value.
P8
Deadband
Sets the amount of deadband in percent
of full scale for relays.
0 (disabled), 0.1,
0.2, 0.5, 1, 2, 5, 10%
SetPoint model
only.