Internal push buttons and valve operations


PB01 INJECT PUSHBUTTON

Pilots RESIN GEL ALARM VALVE (RGA V01) INJECTION CYLCE START VALVE (V02) and disarms the flush cycle.

Must have a signal from AN1 to work.

PB02 REMOTE INJECT PUSHBUTTON

Pilots REMOTE INJECTION VALVE (V01).

Must have a signal from AN1 to work.

PB03 REMOTE STOP PUSHBUTTON

Pilots FLUSH CYCLE SIGNALS VALVE (V10), FLUSH INTERLOCK VALVE (V05) on and INJECTION CYCLE START VAVLE (V02) off.
Stops all functions of the Innovator and arms the flush cycle.

PB04 RGA RESET PUSHBUTTON

Pilots the RESIN GEL ALARM VALVE (RGA V01) valve off. This pushbutton is inside the box and accessible thru the side via small
probe.

PB05

PRIME PUSHBUTTON

Pilots INJECTION GUN VALVE (V06) to allow bypass of PPVS and MPG sensors to allow the Injection gun to dispense material.

Must have a signal from AN1 to work

PB06 STOP PUSHBUTTON

Pilots FLUSH CYCLE SIGNALS VALVE (V10), FLUSH INTERLOCK VALVE (V05) on and INJECTION CYCLE START VAVLE (V02) off.
Stops all functions of the Innovator and arms the flush cycle.

PB07 E STOP

Pilots FLUSH CYCLE SIGNALS VALVE (V10), FLUSH INTERLOCK VALVE (V05) on and INJECTION CYCLE START VAVLE (V02) off.
Stops all functions of the Innovator and arms the flush cycle

This is a maintained button, must be reset to allow machine to work.

PB08 FLUSH PUSHBUTTON

Pilots the RESIN GEL ALARM (RGA V01) valve off and pilots, FLUSH CYCLES SIGNAL VALVE on (V10)

Supplied from FLUSH INTERLOCK VALVE (V05).

PB09 RECIRCULATION PUSHBUTTON

Pilots RECIRCULATION GUN VAVLE (V07)

Supplied from RECIRCULATION INTERLOCK VALVE (V04)

V01

REMOTE INJECTION SEQUENCE START VALVE

In the on position, pilots the INJECTION GUN VALVE (V02) and RESIN GEL ALARM VALVE (RGA V01). Starts the injection
sequence

In the off position, pilots the FLUSH INTERLOCK VALVE (V05), allowing flush sequence to activate.

Triggered by REMOTE INJECT (PB02).

V02

INJECTION SEQUENCE START VALVE

In the on position, pilots the INJECTION GUN VALVE (V06), supplies TAS (RTM ONLY) panel plug and the COUNTER CIRCUIT
VALVE (RGA V03) allowing the injection sequence to start.

In the off position, pilots the FLUSH INTERLOCK VALVE (V05), allowing flush sequence to activate.

Triggered by INJECT (PB01) or REMOTE INJECT (PB02).