- 8 -

E1

E4

E6

E3

E2

a

b

c

a

b

a b

c

d

a

b

c

d

Serial Signal

Duplex

Jumpers

Termination Resistor*

Full

None

E6 a = Transmit

E6 c = Receive

RS485

Half

E6 b + d**

E6 c

RS232

Full

None

None

Serial Signal

Duplex

Jumpers

Termination Resistor*

Full

None

E6 a = Transmit

E6 c = Receive

RS485

Half

E6 b + d**

E6 c

RS232

Full

None

None

*

The termination resistor jumper settings should only be selected if the transmitter is the last
device on an RS485 line longer than 200 feet (60 m).

** Attempting to draw more than the rated current will shut down the output.

To reset communications to 9600 baud, command mode, Custom ASCII protocol, and Address 1,
place a jumper at E1 and power up the transmitter.

Analog Output

Jumpers

Current

E2 a + d

Voltage

E2 b + c

Excitation Output*

Jumpers

5V, 100 mA

E3 a + c; E4 a

10V, 120 mA

E3 a + c; E4 b

24V, 50 mA

E3 b, E4 none

* The termination resistor jumper

settings should only be selected
if the transmitter is the last device
on an RS485 line longer than 200
feet (60 m).

** Or jumper external BTX to BRX

and ATX to ARX (same effect as
internal jumpers).