Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual
Page 20

- 20 -
70
0046
Setup
(applicable to
Scale Meter)
M = Meter
F = Function
D = Display
T = Tare
Bits 3:0
Ctrl In 1 Ctrl In 2 Both Reset
Hex 0 M Reset M Hold M Reset
Hex 1
F Reset Peak D
M Reset
Hex 2
M Hold Peak D F Reset
Hex 3
M Hold Tare
Tare
Hex 4
Peak
Tare
F Reset
Hex 5
M Reset Tare
M Reset
Hex 6
F Reset
Tare
M Reset
Hex 7
T Reset Tare
M Reset
Hex 8
D Blank Tare
M Reset
Hex 9
M Reset D Blank M Reset
Hex A
F Reset D Blank M Reset
Hex B
D Item
Tare
Tare
Hex C
D Item
D Blank F Reset
Hex D
M Reset D Item
M Reset
Hex E
F Reset
D Item
M Reset
Hex F
M Hold
D Item
M Reset
Bit 4
0 = Scale, Offset
1 = Coord of 2 Points
Bit 5
0 = Peak key is Peak 1 = Peak key is Tare
Bit 6
0 = 60 Hz
1 = 50 Hz
Bit 7
0 = No dummy zero 1 = Dummy zero
71
0047
Filter
Bits 3:0 Filtering
Hex 0 = Auto Filter, 1 = Batch 16, 2-9 = Moving
Avg, 2 = .08S, 3 = .15S, 4 = .3S, 5 = .6S, 6 = 1.2S,
7 = 2.4S, 8 = 4.8S, 9 = 9.6S, A = Unfiltered
Bit 4 0 = Low Adaptive
1 = High Adaptive
Bit 5 0 = Display Batch of 16
1 = Display Filtered
Bit 6 0 = Peak of Unfiltered
1 = Peak of Filtered
Bit 7 0 = Alarm source Unfiltered, 1 = Filtered
72
0048
Options
Do Not Use.
73
0049
Serial Config 1
Bits 3:0 Time between Continuous Serial Outputs
Hex 0=.017S, 1=.28S, 2=.57S, 3=1.1S, 4=2.3S,
5=4.5S, 6=9.1S, 7=18.1S, 8=36.3S, 9=1M13S,
A=2M25S, B=4M50S, C=9M40S, D=19M20S,
E=38M41S, F=77M21S
Bits 6:4 Baud Rate
000 = 300, 001 = 600, 010 = 1200, 011 = 2400,
100 = 4800, 101 = 9600, 110 = 19200
Bit 7
0 = Send Unfiltered value, 1 = Send Filtered Val