Page 20

background image

- 20 -

70

0046

Setup
(applicable to
Scale Meter)

M = Meter
F = Function
D = Display
T = Tare

Bits 3:0

Ctrl In 1 Ctrl In 2 Both Reset

Hex 0 M Reset M Hold M Reset

Hex 1

F Reset Peak D

M Reset

Hex 2

M Hold Peak D F Reset

Hex 3

M Hold Tare

Tare

Hex 4

Peak

Tare

F Reset

Hex 5

M Reset Tare

M Reset

Hex 6

F Reset

Tare

M Reset

Hex 7

T Reset Tare

M Reset

Hex 8

D Blank Tare

M Reset

Hex 9

M Reset D Blank M Reset

Hex A

F Reset D Blank M Reset

Hex B

D Item

Tare

Tare

Hex C

D Item

D Blank F Reset

Hex D

M Reset D Item

M Reset

Hex E

F Reset

D Item

M Reset

Hex F

M Hold

D Item

M Reset

Bit 4

0 = Scale, Offset

1 = Coord of 2 Points

Bit 5

0 = Peak key is Peak 1 = Peak key is Tare

Bit 6

0 = 60 Hz

1 = 50 Hz

Bit 7

0 = No dummy zero 1 = Dummy zero

71

0047

Filter

Bits 3:0 Filtering

Hex 0 = Auto Filter, 1 = Batch 16, 2-9 = Moving

Avg, 2 = .08S, 3 = .15S, 4 = .3S, 5 = .6S, 6 = 1.2S,

7 = 2.4S, 8 = 4.8S, 9 = 9.6S, A = Unfiltered

Bit 4 0 = Low Adaptive

1 = High Adaptive

Bit 5 0 = Display Batch of 16

1 = Display Filtered

Bit 6 0 = Peak of Unfiltered

1 = Peak of Filtered

Bit 7 0 = Alarm source Unfiltered, 1 = Filtered

72

0048

Options

Do Not Use.

73

0049

Serial Config 1

Bits 3:0 Time between Continuous Serial Outputs

Hex 0=.017S, 1=.28S, 2=.57S, 3=1.1S, 4=2.3S,

5=4.5S, 6=9.1S, 7=18.1S, 8=36.3S, 9=1M13S,

A=2M25S, B=4M50S, C=9M40S, D=19M20S,

E=38M41S, F=77M21S

Bits 6:4 Baud Rate

000 = 300, 001 = 600, 010 = 1200, 011 = 2400,

100 = 4800, 101 = 9600, 110 = 19200

Bit 7

0 = Send Unfiltered value, 1 = Send Filtered Val