Page 21

background image

- 21 -

74

004A

Serial Config 2

Bits 4:0 Meter Serial Address (0-31) [Non-Modbus]

Hex 0 = Broadcast (01 = 1 to 0A = 10),

0F = 15, 10 = 16, 1F = 31

Bit 5

0 = Continuous Mode, 1 = Command Mode

Bit 6

0 = No Alarm data with readings, 1 = Alarm data

Bit 7

0 = No LF following CR, 1 = LF following CR

75

004B

Serial Config 3

Bits 2:0 for DPM. Data sent in serial output

0 = Reading, 1 = Peak, 2 = Valley,

3 = Rdg + Peak, 4 = Rdg + Valley,

5 = Rdg + Peak + Valley

Bits 2:0 for Scale Meter

0 = Net + Gross

1 = Net only

2 = Gross only

3 = Peak only

4 = Net + Gross + Peak

Bit 3

0 = Termination chars at end of all items

1 = " " at end of each item

Bit 4

0 = Non-latching RTS, 1 = Latching RTS

Bit 5

0 = Normal continuous serial transmission

1 = Special Start & Stop characters

Bit 6

0 = Full Duplex

1 = Half Duplex

76

004C

Serial Config 4

Bits 1:0 00 = No Parity

01 = Odd Parity

10 = Even Parity

Bits 3:2 00 = Custom ASCII 01 = Modbus RTU

10 = Modbus ASCII

Bits 5:4 Modbus ASCII Gap Timeout

00 = 1S, 01 = 3S, 10 = 5S, 11 = 10S

77

004D

Config
(applicable to
DPM)

Bit 0

0 = Linear Curve

1 = Custom Curve

Bit 1

0 = 2-wire RTD Read 1= 2-wire RTD Short

Bits 2 0 = No Auto-tare

1 = Auto-tare

Bits 4:3 Peak button display response

00 = Peak

01 = Valley

10 = Peak then Vall. 11 = Tare

Bits 7:5 000 = Not Rate

001 = Rate x 0.1,

010 = Rate x 1

011 = Rate x 10,

100 = Rate x 100

101 = Rate x 1000

110 = Rate x 10000

77

004D

Config
(applicable to
Scale Meter)

Bit 1

0 = Peak of net value 1 = peak of gross value

Bit 2

0 = Dribble enabled 1 = Dribble disabled

Bit 3

0 = Scale & offset setup method

1 = Reading coordinates of 2 points method