Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual
Page 27
- 27 -
Hex 5 Valley
Peak
FRest
Hex 6 Function Reset External Gate MReset
Hex 7 Meter Hold Peak or Valley FReset
Hex 8 Reset Total A Reset Total B
FReset
Hex 9 Force Alarm1 Force Alarm2
No Action
Hex A Meter Reset Display Blank MReset
Hex B Function Reset Display Blank MReset
Hex C Meter Hold
Display Blank MReset
Hex D Peak or Valley Display Blank
FReset
Hex E Display Blank External Gate MReset
Hex F
Item2
Item3
Item 1 = Neither/Both
Hex F
Tare Enable
Tare (Remote Display Only)
Bit 4
0 = Scale2 using Scale, Offset
1 = Scale2 using Coordinates of 2 Points
Bit 5
0 = Scale1 using Scale, Offset
1 = Scale1 using Coordinates of 2 Points
Bit 6
0 = Blank leading zeros
1 = Display leading zeros
Bit 7
0 = Zero Total upon Power-On
1 = Restore Total upon Power-On
71
0047 Filter
Bits 2:0 1 = .1S, 2 = .2S, 3 = .4S, 4=.8S, 5=1.6S,
6 = 3.2S, 7=6.4S
Bit 3
0 = Low Adaptive, 1 = High Adaptive
Bit 4
0 = Display Unfiltered, 1=Display Filtered
Bit 5
0 = Peak, Valley of Unfiltered
1 = Peak,Valley of Filtered
Bit 6
0 = Adaptive Filter
1 = Conventional Filter
72
0048 Options
Do Not Use.
73
0049 Serial
Config 1
Bits 3:0 Time between Continuous Serial Outputs
Hex 0=.017S, 1=.28S, 2=.57S, 3=1.1S, 4=2.3S,
5=4.5S, 6=9.1S, 7=18.1S, 8=36.3S, 9=1M13S,
A=2M25S, B=4M50S, C=9M40S, D=19M20S,
E=38M41S, F=77M21S
Bits 6:4 Baud Rate
000 = 300, 001 = 600, 010 = 1200, 011 = 2400,
100 = 4800, 101 = 9600, 110 = 19200
Bit 7
0 = Send Unfiltered value, 1 = Send Filtered Val