7 = Remote Display, Value

8 = 1st Value in String

9 = 2nd Value in String

A = 3rd Value in String

B = 4

th

Value in String

C = Remote Display using Start, Stop, Skip,

Show Characters

78

004E Lockout 1

0 = Enabled, 1 = Locked out

Bit 0

Filter

Bit 1

Gate Time, Timeout, Batch, Preset, Pulses, Cutoff

Bit 2

Setup, Config, Display Number

Bit 3

Input Type

Bit 4

Setpoint Programming

Bit 5

Alarm Config, Deviation / Hysteresis

Bit 6

Scale, Offset, Resolution, 2 Coordinates

Bit 7

Slope, Decimal Points

79

004F Lockout 2

0 = Enabled, 1 = Locked out

Bit 0

Change Item# displayed

Bit 1

Calibration

Bit 2

Serial Comm Config

Bit 3

Analog Out Scaling & Setup

Bit 4

Front Panel Meter Reset

Bit 5

Front Panel Function Reset

Bit 6

View Setpoints

Bit 7

View Peak

80

50

Batch
Operation

Bit 0

0 = Display “rEADy” after Reset

1 = Start

Bit 1

0 = Item2 is Grand Total

1 = Item2 is Total Number of Batches

Bit 2

0 = Gate Time resets

1 = Control Input 2 resets

Bit 3

0 = Reset to Zero, Count Up

1 = Reset to SETPT1, Count Down

Bits 5:4 Residual Input

0,2 = Input Discard, Grand Total Discard

1 = Input Accept, Grand Total Discard

3 = Input Accept, Grand Total Accept