- 25 -
For the following, use any starting Register Addresses and any number of Registers.
Register Addr
Dec
Hex
Register Name
Data
Type
Scaling & Decimal Point
49
50
51
52
53
54
55
56
57
58
50
0031
0032
0033
0034
0035
0036
0037
0038
0039
003A
003B
GateTime
TimeOut
Pulses
Total B (Hi word)
Total B (Mid word)
Total B (Lo word)
Total A (Hi word)
Total A (Mid word)
Total A (Lo word)
Cutoff
Calibration
M16
M16
M16
M48
M48
M48
M48
M48
M48
M16
M15
1-19999 (4E1F) Dec Pt =XXX.XX
1-19999 (4E1F) Dec Pt =XX.XXX
1-59999 (4E1F) Dec Pt =XXXXX.
0-65535
SXXX XXXX XXXX XXXX
Sign + Magnitude (PPM)
Data Type B16
Register Addr
Dec
Hex
Register
Name
Bit Significance
65
0041 Alarm
Config 1
Bit 0
0 = AL1 Hi Active
1 = Lo Active
Bit 1
0 = AL1 Enabled,
1 = Disabled
Bit 2
0 = AL2 Hi Active
1 = Lo Active
Bit 3
0 = AL2 Enabled
1 = Disabled
Bit 4
0 = AL1 Non-Latched 1 = Latched
Bit 5
0 = AL2 Non-Latched
1 = Latched
Bit 6
0 = Relay1 Active On
1 = Off
Bit 7
0 = Relay2 Active On
1 = Off
66
0042 Alarm
Config 2
Bits 2:0 # Readings before Alarms 1 & 2.
000 = 1, 001 = 2, 010 = 4, 011 = 8, 100 = 16,
101 = 32, 110 = 64, 111 = 128
Bits 4:3 Setpoint Compare Source
Bit 3
AL1 0 = Deviation
1 = Hysteresis
Bit 4
AL2 0 = Deviation
1 = Hysteresis
Bit 5
0 = Deviation in Menu 1 = Omitted
67
0043 Alarm
Config 3
Bit 0
0 = AL3 Hi Active
1 = Lo Active
Bit 1
0 = AL3 Enabled
1 = Disabled
Bit 2
0 = AL4 Hi Active
1 = Lo Active
Bit 3
0 = AL4 Enabled
1 = Disabled
Bit 4
0 = AL3 Non-Latched 1 = Latched
Bit 5
0 = AL4 Non-Latched 1 = Latched