Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual

Page 19

background image

- 19 -

69

0045

Input Type

Lo Byte Hex value
40-4D

Thermocouple JF, C, KF, KC, NF, NC, EF, EC,

TF, TC, SF, SC, RF, RC

50-5C

RTD pre-2009: 4-wire DIN°F, 4-wire DIN°C,
4-wire ANSI°F, 4-wire°C, 3-wire DIN°F, 3-wire
DIN°C, 3-wire ANSI°F, 3-wire ANSI°C, 2-wire
DIN°F, 2-wire DIN°C, 2-wire ANSI°F, 2-wire
ANSI°C, Short

50-57

RTD post-2009: DIN°F, DIN°C, ANSI°F,
ANSI°C, Ni°F, Ni°C, Cu°F, Cu°C,

60-64 DC 0.2V, 2V, 20V, 200V, 660V
70-73 DC 2 mA, 20 mA, 200 mA, 5A
A0-A2 Ratio 0.2V, 2V, 20V
80-84 RMS 0.2V, 2V, 20V, 200V, 660V
90-93 RMS 2 mA, 20 mA, 200 mA, 5A
C0-C4 Strain 20, 50, 100, 250, 500 mV
D0-D4 Load Cell 20, 50, 100, 250, 500 mV
E0-E4

Ohms 20, 200, 2000, 20K, 200K

70

0046

Setup
(applicable to
DPM)

M = Meter
F = Function
D = Display

Bits 3:0

Ctrl In 1 Ctrl In 2 Both Reset

Hex 0 M Reset M Hold M Reset

Hex 1

F Reset Pk, Vy M Reset

Hex 2

M Hold Pk, Vy F Reset

Hex 3

M Hold Tare

M Reset

Hex 4

Pk, Vy Tare

FReset

Hex 5

Tare

M Reset M Reset

Hex 6

DP2

DP3

DP5 Neither = DP1

Hex 7

DP3

DP4

DP6 Neither = DP2

Hex 8

F Reset D Blank M Reset

Hex 9

M Hold D Blank M Reset

Hex A

Pk, Vy D Blank F Reset

Hex B

Tare

D Blank M Reset

Hex C

Valley

Peak

F Reset

Hex D

Tare

T Reset M Reset

Bits 5:4

Hex 00 Scale using Scale, Offset

Hex 01 Scale using Coordinates of 2 Points

Hex 10 Scale using Reading Coordinates

Bit 6

Spare

Bit 7

0 = 60 Hz, 1 = 50 Hz