81

0051 Alarm

Source

Bits 1:0 Setpoint 2
Bits 3:2 Setpoint 1
Bits 5:4 Setpoint 4
Bits 7:6 Setpoint 3

For each Setpoint: 00 = Filtered Item,

01 = Item1, 10 = Item2, 11 = Item3

82

0052 Analog Out

Setup

Bits1:0 0 = Filtered Item, 1 = Item1, 2 = Item2, 3 = Item3
Bit 2

0 = Current Output, 1 = Voltage Output

83

0053 Scale

Multiplier

Bits 3:0 Scale1 Multiplier
Bits 7:4 Scale2 Multiplier

0 = .00001, 1 = .0001, 2 = .001, 3 = .01,

4 = .1, 5 = 1, 6 = 10, 7 = 100, 8 = 1000,

9 = 10000, A = 100000

84

0054 Trigger

Slope

Bit 0

0 = Positive Slope, B Input

1 = Negative Slope, B Input

Bit 1

0 = Positive Slope, A Input

1 = Negative Slope, A Input

85

0055 Display Item Bits 1:0 1 = Item1, 2 = Item2, 3 =Item3

Bits 3:2 Display Response to Peak Button:

00 = Peak, 01 = Valley, 10 = Peak then Valley

86

0056 Resolution

Bits 3:0 0 = .00001, 1= .0001, 2 = .001, 3 = .01,

4 = .1, 5 = 1, 6 = 10, 7 = 100, 8 = 1000,

9 = 10000, A = 100000

87

0057 System

Decimal
Point

Bits 3:0 DecPt1
Bits 7:4 DecPt2

1 = dddddd., 2 = ddddd.d, 3 = dddd.dd,

4 = ddd.ddd, 5 = dd.dddd, 6 = d.ddddd

Special Characters

88

0058 Recognition

Bits 7:0 ASCII Hex Character

89

0059 Remote Start

Bits 7:0 ASCII Hex Character

90

005A Remote Stop

Bits 7:0 ASCII Hex Character

91

005B Remote Skip

Bits 7:0 ASCII Hex Character

92

005C Remote Show

Bits 7:0 ASCII Hex Character

93

005D Serial Transm. Start

Bits 7:0 ASCII Hex Character

94

005E Serial Transm. Stop

Bits 7:0 ASCII Hex Character

95

005F Modbus Address

Bits 7:0 Hex Value of Decimal Address 1-255

96

60

Reserved

97

61

Reserved

Do not use