81
0051 Alarm
Source
Bits 1:0 Setpoint 2
Bits 3:2 Setpoint 1
Bits 5:4 Setpoint 4
Bits 7:6 Setpoint 3
For each Setpoint: 00 = Filtered Item,
01 = Item1, 10 = Item2, 11 = Item3
82
0052 Analog Out
Setup
Bits1:0 0 = Filtered Item, 1 = Item1, 2 = Item2, 3 = Item3
Bit 2
0 = Current Output, 1 = Voltage Output
83
0053 Scale
Multiplier
Bits 3:0 Scale1 Multiplier
Bits 7:4 Scale2 Multiplier
0 = .00001, 1 = .0001, 2 = .001, 3 = .01,
4 = .1, 5 = 1, 6 = 10, 7 = 100, 8 = 1000,
9 = 10000, A = 100000
84
0054 Trigger
Slope
Bit 0
0 = Positive Slope, B Input
1 = Negative Slope, B Input
Bit 1
0 = Positive Slope, A Input
1 = Negative Slope, A Input
85
0055 Display Item Bits 1:0 1 = Item1, 2 = Item2, 3 =Item3
Bits 3:2 Display Response to Peak Button:
00 = Peak, 01 = Valley, 10 = Peak then Valley
86
0056 Resolution
Bits 3:0 0 = .00001, 1= .0001, 2 = .001, 3 = .01,
4 = .1, 5 = 1, 6 = 10, 7 = 100, 8 = 1000,
9 = 10000, A = 100000
87
0057 System
Decimal
Point
Bits 3:0 DecPt1
Bits 7:4 DecPt2
1 = dddddd., 2 = ddddd.d, 3 = dddd.dd,
4 = ddd.ddd, 5 = dd.dddd, 6 = d.ddddd
Special Characters
88
0058 Recognition
Bits 7:0 ASCII Hex Character
89
0059 Remote Start
Bits 7:0 ASCII Hex Character
90
005A Remote Stop
Bits 7:0 ASCII Hex Character
91
005B Remote Skip
Bits 7:0 ASCII Hex Character
92
005C Remote Show
Bits 7:0 ASCII Hex Character
93
005D Serial Transm. Start
Bits 7:0 ASCII Hex Character
94
005E Serial Transm. Stop
Bits 7:0 ASCII Hex Character
95
005F Modbus Address
Bits 7:0 Hex Value of Decimal Address 1-255
96
60
Reserved
97
61
Reserved
Do not use