Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual
Page 15
- 15 -
Column Number
FC
Action
1
2
3
4
5
6
7
8
9
10
11
12
13
03
03
Request
Response
:
:
MA
MA
FC
FC
RA
NB
RA
DD*
NR
DD*
NR
LRC
LRC
CR
CR
LF
LF
04
04
Request
Response
:
:
MA
MA
FC
FC
RA
NB
RA
DD*
NR
DD*
NR
LRC
LRC
CR
CR
LF
LF
05
05
Request
Response
:
:
MA
MA
FC
FC
RA
RA
RA
RA
WW
WW
WW
WW
LRC
LRC
CR
CR
LF
LF
08
08
Request
Response
:
:
MA
MA
FC
FC
SF
SF
SF
SF
WW
DD*
WW
DD*
LRC
LRC
CR
CR
LF
LF
10
10
Request
Response
:
:
MA
MA
FC
FC
RA
RA
RA
RA
NR
NR
NR
NR
NB
LRC
DD*
CR
DD*
LF
LRC CR
LF
Exception
Response
:
MA FC
+80
EC LRC CR
LF
10. MESSAGE EXAMPLES FOR DEVICE ADDRESS = 01, NO PARITY
Modbus RTU
Modbus ASCII
Example
Action
Ser_4 = 010 Addr = 001
Ser_4 = 020 Addr = 001
Restart Com-
munications*
Request
Response
010800010000B1CB
010800010000B1CB
:010800010000F6crlf
:010800010000F6crlf
Meter Reset
Request
Response
01050001FF00DDFA
None
:01050001FF00FAcrlf
None
Digital Reading
= +25.18
Request
Response
01040003000281CB
010404000009D67C4A
:010400030002F6crlf
:010404000009D618crlf
Write Setpoint
1 = +37.00
Request
Response
0110000100020400000E743624
0110000100021008
:0110000100020400000E7466crlf
:011000010002ECcrlf
Read Setpoint 1
= +37.00
Request
Response
01030001000295CB
01030400000E74FE74
:010300010002F9crlf
:01030400000E7476crlf
First send decimal point, address 0057 as 00 03.
Send -12.34 to
Remote Display
**
Request
Response
01100069000204FFFFFB2EF6E5
01100069000291D4
:01100069000204FFFFFB2E59crlf
:01100069000284crlf
* Suggested as first message after power-up. If device is in Listen-Only mode, no response is
returned.
** 1234 decimal = 000004D2 hex. -1234 = FF FF FB 2E in 4-byte 2’s complement hex. Decimal point
is ignored.
RTU: Bolded last 4 characters indicate the CRC (added automatically by the device).
ASCII: Bolded last 2 characters indicate the LRC ((added automatically by the device).