- 15 -

Column Number

FC

Action

1

2

3

4

5

6

7

8

9

10

11

12

13

03
03

Request
Response

:
:

MA
MA

FC
FC

RA
NB

RA

DD*

NR

DD*

NR

LRC

LRC

CR

CR

LF

LF

04
04

Request
Response

:
:

MA
MA

FC
FC

RA
NB

RA

DD*

NR

DD*

NR

LRC

LRC

CR

CR

LF

LF

05
05

Request
Response

:
:

MA
MA

FC
FC

RA
RA

RA
RA

WW
WW

WW
WW

LRC
LRC

CR
CR

LF
LF

08
08

Request
Response

:
:

MA
MA

FC
FC

SF
SF

SF
SF

WW

DD*

WW

DD*

LRC
LRC

CR
CR

LF
LF

10
10

Request
Response

:
:

MA
MA

FC
FC

RA
RA

RA
RA

NR
NR

NR
NR

NB

LRC

DD*

CR

DD*

LF

LRC CR

LF

Exception
Response

:

MA FC

+80

EC LRC CR

LF

10. MESSAGE EXAMPLES FOR DEVICE ADDRESS = 01, NO PARITY

Modbus RTU

Modbus ASCII

Example

Action

Ser_4 = 010 Addr = 001

Ser_4 = 020 Addr = 001

Restart Com-
munications*

Request
Response

010800010000B1CB
010800010000B1CB

:010800010000F6crlf
:010800010000F6crlf

Meter Reset

Request
Response

01050001FF00DDFA
None

:01050001FF00FAcrlf
None

Digital Reading
= +25.18

Request
Response

01040003000281CB
010404000009D67C4A

:010400030002F6crlf
:010404000009D618crlf

Write Setpoint
1 = +37.00

Request
Response

0110000100020400000E743624
0110000100021008

:0110000100020400000E7466crlf
:011000010002ECcrlf

Read Setpoint 1
= +37.00

Request
Response

01030001000295CB
01030400000E74FE74

:010300010002F9crlf
:01030400000E7476crlf

First send decimal point, address 0057 as 00 03.

Send -12.34 to
Remote Display
**

Request
Response

01100069000204FFFFFB2EF6E5
01100069000291D4

:01100069000204FFFFFB2E59crlf
:01100069000284crlf

* Suggested as first message after power-up. If device is in Listen-Only mode, no response is

returned.

** 1234 decimal = 000004D2 hex. -1234 = FF FF FB 2E in 4-byte 2’s complement hex. Decimal point

is ignored.

RTU: Bolded last 4 characters indicate the CRC (added automatically by the device).
ASCII: Bolded last 2 characters indicate the LRC ((added automatically by the device).