READ ONLY (FC03) – Data Type B16

100

0064

Analog Output
DAC Type

Bits 7:0 0 = none,

1 = 1 output, unipolar (12-bit, pre 2009)
2 = 1 output, unipolar (16-bit, pre 2009)

3 = 1 output, uni or bipolar (16-bit, post 2009)
4 = 2 outputs, unipolar (16-bit, post 2009, not
for Scale Meter)

101

0065

Device Type

Bits 7:0 01 = DPM meter

02 = Scale meter

03 = Counter/timer met. 05 = DPM transmitter
06 = Scale transmitter
07 = Counter/timer transmitter

102

0066

Revision

Bits 7:0 Hex value of Decimal Revision number

103

0067

Overload Value

Bits 7:0 Hex overload value

104

0068

Signal Condi-
tioner Type

Bits 7:0 01 = DC, TC/RTD (pre 2009)

02 = RMS (pre 2009)

03 = Load Cell

22 = RMS (post 2009)

31 = TC (post 2009)

41 = RTD or Ohms (post 2009)

WRITE ONLY (FC10 dec16) – Data Type 2C32

105

0069 Display Data (Hi Word)

Hi word of Remote Data to be displayed.

106

006A Display Data (Lo Word) Lo word of Remote Data to be displayed.

13. COUNTER / TIMER REGISTER ADDRESSES FC03 & FC10 (dec16)

Data Types - as shown
Use high word starting Register Addresses and an even number of Registers.

Register Address

Dec*

Hex*

Register Name

Data

Type

Scaling & Decimal Point

1
2
3
4
5
6
7
8
9

0001
0002
0003
0004
0005
0006
0007
0008
0009

Setpoint 1 (Hi word)
Setpoint 1 (Lo word)
Setpoint 2 (Hi word)
Setpoint 2 (Lo word)
Setpoint 3 (Hi word)
Setpoint 3 (Lo word)
Setpoint 4 (Hi word)
Setpoint 4 (Lo word)
Scale 1Y (Hi word)

2C32
2C32
2C32
2C32
2C32
2C32
2C32
2C32

M32

Dec point same as displayed.

Dec point same as displayed.

Dec point same as displayed.

Dec point same as displayed.

Scale = .00001 x dec value