Basic programming – Controlled Products Systems Group 109837 User Manual
Page 16
16
FAAC MODEL 844 Slide Gate Operator
F
RP
Fig. 38
Fig. 39
TX -FSW - Negative for Power Supply to Photocell
Transmitters (Terminal 11)
If you use this terminal to connect the negative transmitters
of the photocell power, you may, if necessary, also use the
FAIL SAFE function (see advanced programming in Section
5.5.2).
If this function is enabled, the equipment checks operation of
the photocells before every opening or closing cycle.
A.A. - Power Supply to Audio Alarm (Terminal 12)
Connect a 24 VDC - 125mA max audio alarm compliant with
UL325. 31.1.4. The alarm will sound upon two sequential ac-
tivations of an entrapment protection device, continuosly until
the activation of a STOP command. To comply with UL325
the STOP input must be connected to a wired control located
in the line-of-sight of the gate.
5.4.5.
J2 Connector - Rapid Connection to RP
This is used for rapid connection of RP receivers (see Fig.
38). Fit the accessory with the components side toward
connector J1. Insert and remove after cutting power.
5.4.6.
J5 Connector - Rapid Connection to Capacitor
Quick-fit connector for connecting the motor starting
capacitor.
5.4.7.
Double Connector J8 - Limit-Switch Quick Fit
Quick-fit connector for connecting the limit-switch. For
connecting both the MLS magnetic limit-switch and the
inductive limit-switch (Fig. 23 Ref. ) to the operator.
5.5. PROGRAMMING
To program operation of the automated system, access the
"PROGRAMMING" mode with keys
F,+ and - on the cover.
Attention: before attempting to power up the system,
re-position the board's cover to avoid contact with high
voltage parts and to access the push-button keys on the
cover (Fig. 39).
BASIC PROGRAMMING
Display
Function
Default
FUNCTION LOGICS (see table of logics):
= Automatic
= "Stepped" automatic
= "Safety" Automatic
= Semi-automatic
= "Stepped" Semi-automatic
= Dead-man
= "B" Semi-automatic
= Mixed Log. (B opening / C closing)
PAUSE TIME:
This has effect only if automatic logic
was selected.
Adjustable from to
sec. in one-
second steps.
Subsequently, display changes to minu-
tes and tens of seconds (separated by a
point) and time is adjusted in 10-second
steps, up to the maximum value of
minutes.
E.g. if the display shows
, pause
time is 2 min. and 50 sec.
5.5.1.
BASIC PROGRAMMING
To access BASIC PROGRAMMING, press key
F:
• If you press it (and hold it down), the display shows the name of
the first function.
• If you release the key, the display shows the value of the function
that can be modified with keys
+ and -.
• If you press
F again (and hold it down), the display shows the
name of the next function, etc.
• When you reach the last function, press
F to exit the program,
and the display resumes showing the gate status.
The following table shows the sequence of functions
accessible in BASIC PROGRAMMING:
Programming is divided in two parts:
BASIC and ADVANCED.
+
-
F