Figure 4-1 motor does not stop flowchart – CONTREX ML-TRIM User Manual
Page 114

4 - 12
Figure 4-1 Motor Does Not Stop Flowchart
Yes
Motor Does Not Stop
MP-53 =
1000 (F–Stop)
J5, Pin 6 is
shorted to
common
Remove wire at J2, Pin 1
Measure voltage with
respect to J2, Pin 2
Voltage = “0”
MP-53 =
0100 (R–Stop)
MP-53 =
0010 (Run)
MP-53 =
0001 (Jog)
Wiring to
Motor Drive
is correct?
Consult Tech
Support
1-800-342-4411
J5, Pin 7 is
shorted to
common
Open
J5, pin 6 and
J5, pin 9
No
Problem
Corrected
No
Problem
Corrected
No
Yes
Yes
Yes
No
No
Yes
No
Yes
Yes
No
No
No
No
Yes
Yes
Open
J5, Pin 7
Drive
Calibration
is correct?
No
No
No