Cmf-a sensor installation – Fluid Components International CMF Series Guide User Manual
Page 2
FLUID COMPONENTS, INTL
FlexCOR
TM
Model CMF Series Coriolis Flow Meter 2 Doc. No. 06EN003318 Rev. B
CMF-A Mounting Bracket and Position
The mounting brackets supplied with the CMF-A instrument must always be used. The unit must be mounted on a wall or
steel frame (vibration-free).
SENSOR IDENTIFICATION
Remote Mount
Configuration
CMF-B Through F
CMF-A
Nipple
Ground
(Ex-applications)
Bracket
Support
Process connections
Sensor
Plug
CMF-A Plug Orientation
To obtain the optimum performance, the plug should be mounted as shown. The plug can be turned within the angles stated.
Plug
Plug
Plug
Transmitter,
Hazardous Location,
Integral Mount
Transmitter,
Weather Proof,
Integral Mount
Horizontal CMF-A Mounting in Pipe for Liquid or Gas
Horizontal mounting is recommended in low flow liquid so that air bubbles
are easier to remove.
For liquid applications, locate the sensor low in the pipe system in order to
avoid under-pressure in the sensor and consequent air separation in the
liquid. Due to the capillary tube effect, the sensor is not self emptying.
Horizontal mounting
· Gas applications
Horizontal mounting
· Liquid applications
The mounting bracket supplied with the CMF-A
instrument must always be used. The unit must be
mounted on a wall or steel frame (vibration-free).
The plug is used as an indicator for the mounting
position of the sensor. The plug should always be
placed within 5° top center of vertical.
Nipple
Ground
(Ex-applications)
Bracket
Support
Media Input (Preferred)
Process connections
Sensor
Plug
Media Output (Preferred)
Process Connection
CMF-A SENSOR INSTALLATION