Installationandwiring
Type 8025 /8035 Batch
7.6.6 Wiring a wall-mounted version
Only▶move▶the▶selectors▶when▶the▶power▶supply▶is▶off.
Insert▶the▶supplied▶stopper▶gaskets▶into▶the▶unused▶cable▶
glands▶to▶ensure▶the▶tightness▶of▶the▶device.
•▶ Unscrew▶the▶unused▶cable▶gland.
•▶ Remove▶the▶transparent▶disk.
•▶ Insert▶the▶supplied▶stopper▶gasket.
•▶ Screw▶the▶nut▶of▶the▶cable▶gland.
▶
→
Install▶the▶device▶as▶described▶in▶chap.▶„7.4“.
▶
→
Set▶the▶selectors▶"SENSOR▶TYPE",▶"SENSOR▶SUPPLY"▶and▶
"LOAD":▶see▶„Tab.▶4“▶page▶29.
▶
→
If▶the▶compact▶version▶of▶the▶8025▶Batch▶is▶energized▶with▶a▶
115/230▶V▶AC▶power▶supply,▶set▶selector▶
D
▶as▶shown▶in▶„Fig.▶
Selector▶
D
▶makes▶it▶possible▶to▶configure▶the▶supply▶voltage▶of▶
the▶device▶in▶a▶115/230▶V▶AC▶version.
▶
→
Energize▶the▶
device▶with▶
a▶230▶V▶AC▶
voltage.
D
230V
115V
▶
→
Energize▶the▶
device▶with▶
a▶115▶V▶AC▶
voltage.
Fig. 25: Selector of the supply voltage on a 115/230 V AC version
▶
→
Loosen▶the▶nuts▶of▶the▶cable▶glands.
▶
→
Insert▶each▶cable▶through▶a▶nut▶than▶through▶the▶cable▶gland,▶
using▶the▶cable▶glands▶as▶shown▶in▶„Fig.▶26“.
Cable▶of▶the▶flow▶
sensor
Cables▶of▶the▶relay▶
outputs▶DO2▶and▶
DO3
Power▶supply▶cable▶
12-36▶V▶DC▶or▶
115/230▶V▶AC
Cable▶of▶the▶digital▶
inputs▶and▶the▶DO1▶
and▶DO4▶outputs
Fig. 26: Using the cable glands
▶
→
On▶a▶115/230▶V▶AC▶fed▶wall-mounted▶version,▶remove▶both▶
terminal▶blocks▶(marked▶6▶and▶7▶in▶„Fig.▶10“)▶from▶the▶housing.