English, See▶chap.▶ „7.6.7“. selector, See ▶„fig.▶29“▶page▶33. selector – Burkert Type 8035 User Manual
Page 26
24
Installationandwiring
Type 8025 /8035 Batch
2
A
5
B
C
6
1
CURRENT
SOURCE
SINK
BINARY
PE
PE
PE
PE
DI1
DI2
DI3
DI4
DO4
ISOG
FLOW
SENSOR
L+
L-
PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
SUPPLY
NC
COIL
PULSE INPUT
NPN/PN
P
2
1
3
PE
+
-
SENSOR
SUPPL
Y
LOAD
+5V
L+
(L+)-12V
COIL/PNP
39K
470
2.2K
SENSOR TYPE
COIL
NPN/PNP
DO2
DO3
OF
FO
N
3
4
terminal block 1
•▶ NC:▶not▶connected
•▶ L+:▶V+▶(positive▶voltage)
•▶ L-:▶0V▶(power▶supply▶ground)
•▶ PE:▶protective▶earth,▶factory▶wired
•▶ P-:▶negative▶transistor▶output▶(DO1)
•▶ P+:▶positive▶transistor▶output▶(DO1)
terminal block 2
PE:▶shieldings▶of▶the▶power▶supply▶cable▶and▶the▶input▶/▶output▶
cables
terminal block 3:▶wiring▶the▶DO2▶relay▶output.
terminal block 4:▶wiring▶the▶DO3▶relay▶output.
terminal block 5 "flow sensor": Wiring▶the▶remote▶flow▶
sensor.▶The▶wiring▶depends▶on▶the▶type▶of▶output▶signal▶originating▶
from▶the▶flow▶sensor:▶see▶chap.▶„7.6.7“.
terminal block 6 "binAry"
•▶ DI1▶to▶DI4:▶4▶digital▶inputs
•▶ DO4:▶transistor▶output
•▶ ISOG:▶ISOGND,▶ground▶common▶to▶the▶4▶digital▶inputs▶and▶the▶
transistor▶output▶DO4.
•▶ PE:▶cable▶shielding
selector
A
:▶see▶chap.▶„7.6.7“.
selector
B
:▶see▶„Fig.▶29“▶page▶33.
selector
C
:▶see▶chap.▶„7.6.7“.
Fig. 18: Terminal assignment of a 12-36 V DC fed panel-mounted
or wall-mounted version
English