Outputs wiring, Output on/off 1250 hz, Output 0-4÷20ma – Burkert Type 8055 User Manual
Page 15
SE 56
15
210_EN_BU_4_3_5X.d
oc
16 (out1)
18 (out2)
17 (out1)
19 (out2)
43V
30
29
43V
24V COMMON
+24V INTERNAL
0/4..20mA OUT
mA
9 (+)
10 (-)
I
Output on/off 1250 Hz
Opto-insulated output with collector and
emitter terminals floating and freely
connectable
Maximum switching voltage: 40 Vdc
Maximum switching current: 100mA
Maximum saturation voltage between
collector and emitter @100mA: 1,2V
Maximum switching frequency (load on
the collector or emitter, RL=470
Ω
,
VOUT=24Vdc): 1250Hz
Maximum reverse current bearable on the
q Opto-insulated output
q Maximum load 1000 ohm
q Maximum voltage without load 27 Vdc
q Refresh frequency equal to the sample frequency
of the connected sensor
q protected against persistent over voltages till 30
Vdc
q Opto-insualted output with collector and emitter terminals
floating and freely connectable. In order to get the maximum
speed performances it is necessary to connect the emitter to
the common terminal of the outputs (0V), while the load has
to be on the collector. This output is internally connected to
the power supply source 24 Vdc available on the terminal
block.
q Maximum switching voltage: 40Vdc
q Maximum switching current: 100mA
q Maximum saturation voltage between collector and emitter
100mA, load on the collector and internal power supply: 0,3V
q Maximum saturation voltage between collector and emitter
100mA, load on the emitter and internal power supply: 3V
q Maximum switching frequency, load on the collector and
internal power supply: (RL=470
Ω
, VOUT=24Vdc): 12500Hz
q Maximum switching frequency, load on the emitter or
external power supply: (RL=470
Ω
, VOUT=24Vdc): 2500Hz
q Insulation from the other secondary circuits (except 24V and
4…20mA outputs): 500 Vdc
OUT 1/OUT 2 standard - OUT 3/OUT 4 with modules (page 9)
Only with ME 201 module
Output on/off 12500 Hz
The converter detect a loss of load on the 4÷20mA output; to disable this
function set the value "mA Val. Fault" to 0 ( pag 28 Pos. 4.7)
OUTPUTS WIRING
Output 0-4÷20mA