LED Status Display

The device status will be indicated by 2 LEDs ("Power" and "MNS").

Once electrical power has been applied (connection of the network line), the following functional tests of
the two-coloured MNS LED are carried out:

• LED lights up green for a short time (ca. ¼ s).

• LED lights up red for a short time (ca. ¼ s).

• LED dark.

Once the functional tests have been completed, the MNS LED can indicate the device status as shown in
the table below.

Status of the MNS LED

Name of the LED

Type / Colour

Function

POWER

Single-colour, green

LED lit up: device has electrical power

MNS

Two-colour,

red / green

Corresponds to MNS-LED according to DeviceNet
specification (MNS Module Network Status)

LED

state

Device status

Explanation / Correction of problem

Dark

No power /
not online

- No power supply to device.
- Device has not yet finished the duplicate MAC ID Test (test lasts approx. 2s).
- Connect additional devices if the device is the only network participant.
- Replace the device.

Green

On-line, connection
to Master exists

- Normal operational status with connection made to Master.

Green
blinking

On-line, no
connection to

Master

- Normal operational status without connection made to Master.

Red

blinking

Connection

time-out

- One or more connections are in the Time-Out state.
- Make new connection via the master to ensure that the I/O data will by

transmitted cyclically.

Red

Critical fault

- Another device with the same MAC ID in the network > change MAC ID and

restart.

- BUS OFF as a result of communication problems.
- Check the baud rate: replace the device if necessary.