Handling the flat cable clamp
Contact is achieved in the form of a penetration technique using the flat cable clamp for ASI from cables.
Electrical connection is achieved in the process without cutting and skinning the cable.
NOTE
Close the second cable aperture using a cable seal if the flat cable terminates in the clamp
(final connection).
Connecting the flat cable clamp with conductor plug and moulded cable
with an ASI flat cable
Loosen both screws on the flat cable clamp.
Separate the upper part of the flat cable clamp from the lower part.
Lay the ASI flat cable in the correct position.
If the flat cable terminates here:
Insert the flat cable seal into the aperture in the correct position.
Place the upper part of the flat cable clamp onto the lower part.
Tighten the screws.
Done!
The electrical connection to the ASI cable has been produced.
Flat cable seal for flat cable clamp
Technical data for the ASI circuit board
Inputs
3 sensors S1 top S3, pnp plus-switching
Supply via the AS interface (24 V +20 % / -10 %), short-circuit proof, current
limited to 60 mA
Switch level High signal
≥
10 V
Limitation of input current
≥
6.5 mA, input current Low signal
≥
1.5 mA
Outputs
3 valves V1 - V3
max. 3 x 1 W
Power reduction after approx. 100 ms, with integrated Watch-Dog function
Programming data
I/O-Code
7 hex (4 outputs and 4 inputs)
ID-Code
F hex (see following table for bit allocation); extended ID codes 1 and 2 = F hex
Profile
7.F