Number of connectable control heads and maximum length of the
bus line

I. ASI standard case

A maximum of 31 control heads can be attached to a bus line in the standard case.

According to ASI specifications the bus cable may be a maximum 100 m long.

NOTE

When using other cable diameters, the maximum cable length also changes (refer to ASI
specification).

Process data

Data bits for inputs (sensor and prox. switches):

Data bits for outputs (actuators and valves):

Parameter bits: not used

Bit No.

Sensor

Value allocation

Bit 0

S1 (sensor 1)

0 Prox. switch 1 OFF

1 Prox. switch 1 ON

Bit 1

S2 (sensor 2)

0 Prox. switch 2 OFF

1 Prox. switch 2 ON

Bit 2

S3 (terminal for add. prox. switch)

0 Prox. switch 3 OFF

1 Prox. switch 3 ON

Bit 3

Not used

always 0

Bit No.

Valve

Value allocation

Bit 0

V1 (Valve 1)

0 Valve 1 OFF

1 Valve 1 ON

Bit 1

V2 (Valve 2)

0 Valve 2 OFF

1 Valve 2 ON

Bit 2

V3 (Valve 3)

0 Valve 3 OFF

1 Valve 3 ON

Bit 3

Not used

always 0