Installation of the control head

Flange adaptor

To mount the control head type 1066 on a process valve from a different manufacturer, you need an
adapter with customized flange (flange adapter) and a customized switching knob (see also Data Sheet).
The connecting part for the control head is Bürkert-specific. The flange component must be adapted to
the shape of the process valve. The drawing below shows an application for a special process valve. The
control head can be installed in any position, but preferably with the cover at the top.

When making your own flange, comply exactly with the following parameters:

Dimensions

Number of sealed positions

Dimension for the O-ring

Measurement tolerance

Material data

Main dimensions for the flange adapter

ATTENTION!

A centring device is necessary for the installation of the flange adapter. The
maximum permissible deviation is ± 0.1 mm. If this tolerance is exceeded, there is the
danger that the proximity sensors may not function correctly.

Use a special installation sleeve to avoid exceeding this tolerance.

NOTE

Please request detailed dimensional drawings if you are manufacturing your own flange
adapter.

Cylindrical adapter part

Custom flange part