1066 - 23

I

NSTALLATION

AND

C

OMMISSIONING

english

II. ASI version with extended address range (A/B Slave)

1 Master can communicate with 62 Slaves with the ASI version with extended address range (A/B Slave).
As in the standard case, the bus cable with extended address range according to ASI specifications my be
a maximum 100 m long.

ATTENTION!

If an A/B Slave device is being used as a replacement for a standard device, a
configuration error arises due to the different ID codes!

Differences in the addressing of ASI variants

Parameters

ASI Standard device

ASI device for A/B Slave addressing

Number Slaves / Master

31

62

I/O Code

7 hex

7 hex

ID Code

F hex

A hex

Extended ID1

F hex

7 hex

Extended ID2

F hex

E hex

Profile

S-7.F.F

S-7.A.E

Characteristics of the A/B Slave variant compared with the standard case

• 62 Slaves per Master

• The yellow OUT 4 LED on the ASI circuit board is no longer controllable, since the fourth output bit

used up to now is now used for the addressing.

• Limitations in power supply due to the nominal current of the inductors:

Only 2 solenoid valves can be connected at the same time; the third solenoid valve can only be
hooked up after 100 ms have passed.

NOTE

Maximum cable lengths also vary when other cable cross sections are used (see ASI