Disassembly

13.2. Disassembly the pneumatic

control unit

procedure:
1. Pneumatic connection

DangEr!

risk of injury from high pressure!
• Before dismounting lines and valves, turn off the pressure and

vent the lines.

Loosen the pneumatic connection.

Series 20xx:
Loosen the pneumatic connection between Pneumatic Control
Unit and actuator.

2. Electrical connection

DangEr!

risk of electric shock!
• Before reaching into the system, switch off the power supply

and secure to prevent reactivation!

• Observe applicable accident prevention and safety regulations

for electrical equipment!

Circular plug-in connector:

Loosen the circular connector.

Cable gland:

Open the Pneumatic Control Unit: unscrewing the transparent
cap in an anticlockwise direction.

Unscrew the screw terminals and pull out cables.

3. Mechanical connection

Loosen the fastening screws.

Remove the Pneumatic Control Unit upwards.

Pneumatic

Control Unit

Transparent cap

Fastening screws

(2x)

Pneumatic

connections

Pneumatic con-

nection to the

actuator

Actuator

Cable gland

Series 21xx

Series 20xx

Fig. 23: Disassembly the Pneumatic Control Unit

english

Type 8690 Ex