beautypg.com

Rotating the actuator module – Burkert Type 8690 User Manual

Page 21

background image

21

Installation

control function

pneumatic connection type 8690
with actuator
pilot air outlet
type

8690

pilot air port
actuator

a

Process valve closed
in rest position
(by spring force)

2

1

lower pilot air port
of the actuator

2

2

should be con-
nected to the
upper pilot air port
of the actuator

B

Process valve open
in rest position
(by spring force)

2

1

upper pilot air port
of the actuator

2

2

should be con-
nected to the
lower pilot air port
of the actuator

i

Process valve closed
in rest position

2

1

lower pilot air port
of the actuator

2

2

upper pilot air port
of the actuator

Process valve open
in rest position

2

1

upper pilot air port
of the actuator

2

2

lower pilot air port
of the actuator

Tab. 6: Pneumatic connection to actuator

7.4.

rotating the actuator module

The actuator module (Pneumatic Control Unit and actuator)
can be rotated for straight seat valves and angle seat valves
only!

The position of the connections can be aligned steplessly by rotating the
actuator module (Pneumatic Control Unit and actuator) through 360°.

Only the entire actuator module can be rotated. The Pneu-
matic Control Unit cannot be rotated contrary to the actuator.
The process valve must be in the open position for alignment
of the actuator module!

DangEr!

risk of injury from high pressure!
• Before dismounting lines and valves, turn off the pressure and

vent the lines.

procedure:

Clamp valve body in a holding device (only required if the process
valve has not yet been installed).

Control function A: Open process valve.

english