beautypg.com

English – Burkert Type 8642 User Manual

Page 41

background image

8642/142 791 - 39

english

CHECK_BACK

Detailed information of the device, bitwise coded.
More than one message possible at once.

Bit

Information

0

in “Fail-save” position

8

Valve opens

9

Valve closes

16

The number of switching cycles pre-defined in
TRAVEL_COUNT_LIM has been exceeded

20

Time for opening exceeded

21

Time for closing exceeded

1 = active
0 = inactive

CHECK_BACK_MASK Definition of supported CHECK_BACK informtion bits

1 = supported
0 = not supported