beautypg.com

English, 2 setting the station addresses, 3 led display – Burkert Type 8642 User Manual

Page 14: 4 watchdog, 5 gsd file

background image

12 - 8642/142 791

english

4.2.2 Setting the Station Addresses

DIP switch 1 to 7

Bit 1 to Bit 7

NOTE

The DIP switches are only read in when the unit is switched on.

In the PROFIBUS-PA, each station is given an address. These addresses are

set

up using the DIP switches 1 to 7.

The permissible address range lies between 3 and 124

4.2.3 LED Display

The LED lights up when the unit is in cyclic data traffic.

4.2.4 Watchdog

In order to detect errors better, we recommend to operate the device in the
cyclic data communication with "DP watchdog".

4.2.5 GSD file

Use the GSD file Buer6521.GSD, which is to be found under the ID no. 142791
on the enclosed data memory. The associated bitmaps are also there.

Settings:

DIP-1

DIP-2

DIP-3

DIP-4

DIP-5

DIP-6

DIP-7 Address

ON

ON

OFF

OFF

OFF

OFF

OFF

3

..

OFF

OFF

ON

ON

ON

ON

ON

124

ON

OFF

ON

ON

ON

ON

ON

125

OFF

ON

ON

ON

ON

ON

ON

126*

* Delivery state: Address 126

permitted address

range

3 ... 124

DIP switches 9 - 12 are not used.

NOTE

If switch 8 is in the ON position, the internal address is used!
This address can be set up via the field bus.