Parameter

Description

TRAVEL_COUNT

Number of cycles from OPEN to CLOSE and
CLOSE to OPEN or inverse.

TRAVEL_COUNT_LIM

Limit for TRAVEL_COUNT; at 0
TRAVEL_COUNT_LIM will not be processed. If
the LIMIT value is exceeded, the corresponding
bit will be set in CHECK_BACK.

SELF_CALIB_CMD

Initiation of a device-specific calibration
procedure, manufacturer specific 0-default.

y = 0

active undamped

y = 1

active damped

x = 0

sensor indicates “valve open”

x = 1

sensor indicates “valve closed”

TRAVEL_TIME_OPEN_LIM

Limit for the time in 10 milliseconds between the
change of the state from CLOSE to
OPEN; with 0, the time is not processed.
If the value is exceeded, the corresponding bit
will be set in CHECK_BACK.

TRAVEL_TIME_CLOSE_LIM

Set-value for the time in seconds between the
change of state from “open” to “closed”; with 0,
the time is not processed. If the value is
exceeded, the corresponding bit will be set in
CHECK_BACK.

The

View Object Standard Parameters

Rel. index Variable

View_1

View_2

View_3

View_4

1

ST_REV

2

2

TAG_DESCRIPTION

3

STRATEGY

4

ALERT_KEY

5

TARGET_MODUS

6

MODUS_BLK

3

7

ALARM_SUM

8

Table 15:

View Object of the Standard Parameters

x y