Burkert Type 6106 User Manual
Page 10

10
Technical data
6.5.2. Use in temperature class T6
Ignition protection type Ex ia, Gas group II C
Temperature
class
Max. per-
mitted
ambient tem-
perature [°C]
Assembly
Max. per-
mitted power
consumption
[W]
T6
-40 ... +60
Block
assembly
0.4
-40 ... +55
0.5
-40 ... +50
0.7
-40 ... +45
0.9
-40 ... +40
1.1
-40 ... +60
Individual
0.7
-40 ... +55
0.9
-40 ... +50
1.1
The maximum permitted power depends on the max.
ambient temperature, the temperature class and the
installation.
6.5.3. Use in temperature class T5
Ignition protection type Ex ia, Gas group II C
Temperature
class
Max. per-
mitted
ambient tem-
perature [°C]
Assembly
Max. per-
mitted power
consumption
[W]
T5
-40 ... +75
Block
assembly
0.4
-40 ... +70
0.5
-40 ... +65
0.7
-40 ... +60
0.9
-40 ... +55
1.1
-40 ... +75
Individual
0.7
-40 ... +70
0.9
-40 ... +65
1.1
6.5.4. Use in temperature class T4
Ignition protection type Ex ia, Gas group II C
Temperature
class
Max. per-
mitted
ambient tem-
perature [°C]
Assembly
Max. per-
mitted power
consumption
[W]
T4
-40 ... +100
Block
assembly
0.7
english
PTB 01 ATEX 2175