beautypg.com

Burkert Type 2036 User Manual

Page 24

background image

24

Assembly

Type 2036

control function a:

Connect the control medium to the pilot air port 1 and/or 3
(see "Fig. 17").

control function B:

Connect the control medium to the pilot air port 2 and/or 4
(see "Fig. 17").

Silencer

Connect the silencer into the free air discharge connection
(see "Fig. 17").

Pilot air port

2 (P2)

Pilot air port
4 (P4)

Pilot air port
3 (P3)

Pilot air port

1 (P1)

actuator 1

(left)

actuator 2
(right)

Fig. 17: Pneumatic connection

actuator
version

actuator 1

actuator 2

cf

connection

cf

connection

D11, D55
CFA/CFA
(NC/NC)

CFA,
NC

Pilot air

P1

P2: air discharge

CFA

Pilot air

P3

P4: air discharge

D12
CFA/CFB
(NC/NO)

CFA,
NC

Pilot air

P1

P2: air discharge

CFB

Pilot air

P4

P3: air discharge

D21
CFB/CFA
(NO/NC)

CFB,
NO

Pilot air

P2

P1: air discharge

CFA

Pilot air

P3

P4: air discharge

D22
CFB/CFB
(NO/NO)

CFB,
NO

Pilot air

P2

P1: air discharge

CFB

Pilot air

P4

P3: air discharge

Tab. 4: Pneumatic connection for actuator versions

CFA, NC :

Valve normally closed by spring action

CFB, NO :

Valve normally open by spring action

Numbers for

indicating

actuator 1

Numbers for
indicating
actuator 2

Fig. 18: Cover film

english