Assembly

6.2.1 installation position general

installation for self-drainage of the body

It is the responsibility of the installer and operator to ensure
self-drainage.

installation for leakage detection

One of the bores (in the actuator base) for monitoring
leakage must be at the lowest point.

6.2.2 installation position 2/2-way valve

• The piston-controlled diaphragm valve can be installed in any

position, preferably with the actuator face up.

To ensure self-drainage:

Install body at an angle α = 10° to 40° to the horizontal
(see „Fig. 2“).

Maintain an inclination of 1° – 5°.

There is a mark on forged and cast bodies, which must face

upwards (12 o’clock position, see „Fig. 3“).

One of the bores (in the actuator base) for monitoring leakage,

must be at the lowest point.

α

Angle α: 10° to 40°
Inclination to the line axis 1° ... 5°

Fig. 2:

Installation position for self-drainage of the body

Marking for self-draining
inclination

Fig. 3:

Mark for correct installation position

english

Type 2030, 2031, 2031 K, 2032,

2033, 2037