Wiring a version with double inductive 2-wire, Namur switch – Burkert Type 1062 User Manual
Page 32
32
Installationandwiring
Type 1062
+
-
A
+
-
200 mA max.
+ -
1062
10-30 VDC
500 mA
+
-
A
200 mA max.
+ -
Power supply
Load 1
Reaction speed according
to the max. load
Green light (valve open
detection)
Orange light
(voltage present)
Load 2
Valve open
switch
Valve closed
switch
Red light (valve closed
detection)
Fig. 15: Wiring a version with two inductive 3-wire switches in
PNP mode, valve open and valve closed detection
8.2.5 Wiring a version with double
inductive 2-wire nAmuR switch
Respect the maximum allowable characteristics of the circuit
established with an inductive NAMUR switch shown in the table
below.
Max.
authorised
ambient
T°
Category
T°
class
Ii
[mA]
(with
resistive
limit)
Pi
(mW)
U
(V)
Ci
(nF)
Li
(µH)
100 °C
II 2G
T4
60
200
20
180
350
85 °C
II 2G
T5
60
200
20
180
350
80 °C
II 2G
T5
60
200
20
180
350
70 °C
II 2G
T6
60
200
20
180
350
english