Troubleshooting – Dynasonics Fusion Water Flow Meter User Manual

Page 37

background image

37

Troubleshooting

Display does not
illuminate

1. Check DC voltage at terminal strip.
2. Check display ribbon cable.

3. FUSION meters are equipped with

automatic reset fuses.

Output does not
match displayed

flow value

1. Verify that 4-20mA or Rate PULSE is

properly selected in the OUTPUT

selection.

2. Check full flo span value entry—ensure

it matches receiving device.

3. PULSE outputs—verify proper pull-up

jumpers are in place.

4. Utilize 4-20mA Test and PULSE test to

simulate outputs to receiving devices.

Unstable flow
readings

1. Increase straight plumbing at meter

inlet.

2. Change response to medium or slow.
3. Increase damping value.

Fusion indicates
flow when none is

present

1. Verify earth ground connection.
2. Verify that check valves are operating

properly—shut manual valve.

3. Perform zero capture—see software

functions.

EMPTY PIPE
indication

1. Pipe is not filled with liquid.
2. Flow is off, but the liquid within the

sensor is degassing—the error will
clear when gas clears.