Dynasonics Fusion Water Flow Meter User Manual
Page 28

28
AGC MODE—Automatic Gain Control Mode of Operation
NORMAL - Standard Configuration
MANUAL - AGC disabled
Select the desired mode of operation. A basic understanding of
the AGC logic is required in order to know when to use any 
selection other than NORMAL. 
When the unit is powered up, there is a delay before the unit 
begins transmitting sound into the pipe. During this time, the 
signal strength is measured, and a base signal level is obtained. 
Typically this is a value of about 20. The unit measures flow by 
measuring the Doppler frequency shift. The frequency shift is 
approximately 120Hz per foot per second. For every foot per 
second increase in velocity, the signal strength should increase 
by 1. The unit automatically adjusts the gain and selects the 
proper hardware filter for the measured velocity. The control can 
be observed when the DISPLAY mode is set to DOP DIAG. 
When NORMAL is selected, the unit will automatically control the 
gain and front end hardware filter for optimum measurement of 
the Doppler signal. 
For applications where the flow is constant, but you may need to 
tune the unit to filter out extraneous noise, select the MANUAL 
mode. Typically, this would only be required at very low flow 
rates. When MANUAL mode is selected, the GAIN POT and 
FILTER settings are manually set. Automatic control is disabled. 
 
GAIN POT—Digital Gain Pot 
 0-64 
Using the arrow keys, increase or decrease the numerical value 
to set the signal gain level. Typically, optimum flow measurement 
is made when this value is between 10 and 50. Use the lowest 
value that provides an accurate and stable flow reading. This 
adjustment must be made in conjunction with the FILTER 
setting, and may be an iterative process. 
 
FILTER—Hardware Filter Selection 
NONE - No Filter
LOW - (1600Hz Cutoff)
