Chiller Operation and Maintenance

”‡••—”‡ƒ†‡’‡”ƒ–—”‡‘‰

A log of temperatures and pressures should be taken
regularly. Periodically conduct a visual inspection of the
chiller to identify problems before they reach the point of
failure. As with any mechanical system, it is necessary to
…‘†—…–ƒ•‡”‹‡•‘ˆ…Ї…•–‘–Їދƒ‘‘Ž…Š‹ŽŽ‡”–‘…‘Ƥ”
correct operation.

Maintaining a Daily Log

Date

SUN

MON

TUE

WED

THU

FRI

SAT

&KLOOHG:DWHU(QWHULQJ
7HPSHUDWXUH
&KLOOHG:DWHU/HDYLQJ
7HPSHUDWXUH
&RQGHQVHU:DWHU
(QWHULQJ7HPSHUDWXUH
&RQGHQVHU:DWHU
/HDYLQJ7HPSHUDWXUH
6RXUFH:DWHU
(QWHULQJ7HPSHUDWXUH
6RXUFH:DWHU/HDYLQJ
7HPSHUDWXUH
&KLOOHG:DWHU
3UHVVXUH'URS
&RQGHQVHU:DWHU
3UHVVXUH'URS
6RXUFH:DWHU
3UHVVXUH'URS
)DXOWV1RWH%\
0RGXOH1XPEHU

Chiller No.

Technician

Daily

• A daily operational log should be kept.

• Perform visual inspection.

• Record entering and leaving chiller water and condenser

water temperatures and pressures.

• Note any problems that may exist and immediately plan

for further investigation. If repair is necessary, schedule
for earliest possible date.

• Properly document all data taken.

Weekly

• Review daily log from previous week.

• Perform visual inspection.

• Properly document all data taken.

• Note any problems that may exist. Immediately plan

for further investigation. If repair is necessary, schedule
for earliest possible date.

Quarterly

• Check the master and module control panel operating

parameters and set points.

• Check temperature drop/rise on each individual

heat exchanger.*

• Check compressor oil level.

• Check compressor oil color.

• Ї…™ƒ–‡”ƪ‘™”ƒ–‡•ƒ†’”‡••—”‡†”‘’•ƒ…”‘••

evaporator and condenser heat exchangers.

• Properly document all data taken.

• Check all electrical connections for tightness.

* The temperature drop/rise on a fully loaded (both

compressors) heat exchanger is generally 10°F. If only one
compressor is running the temperature drop/rise will be
approximately 5°F. Some projects are designed to have a
higher or lower temperature drop on either the evaporator
or the condenser depending on application. Consult your
•’‡…‹Ƥ…’”‘Œ‡…–„ƒ’‡”ˆ‘”ƒ…‡•Ї‡–ˆ‘”–Ї•‡˜ƒŽ—‡•Ǥˆ
the temperature drop/rise is greater than the design, your
Їƒ–‡š…Šƒ‰‡”ƒ›‡‡†–‘„‡„ƒ…ƪ—•Ї†‘”–Ї•–”ƒ‹‡”
may need to be cleaned.

Annual

• ƒ…ƪ—•ŠƒŽŽŠ‡ƒ–‡š…Šƒ‰‡”•Ǥˆˆ‘—Ž‹‰‹••—•’‡…–‡†—•‡

only ClimaCool recommended de-scalers (see Chemical
Clean In Place Washing on page 31).

• Remove and clean all waterside strainers.

• Manually operate all waterside isolation valves,

if provided, on each module.

• Check all electrical connections for tightness.

• Perform leak check on all refrigerant circuits.

• Check all header piping couplings for tightness.

• Check oil level and color on each compressor.

• Check and test all refrigerant safeties for proper operation.

• Check all peripheral systems for proper operation.

• Check and test CoolLogic Control System.

• ‡”‹ˆ›•‡–’‘‹–•ǡ•‡•‘”•ƒ†‰‡‡”ƒŽ…‘–”‘Ž…‘Ƥ‰—”ƒ–‹‘Ǥ

• Properly document all data taken.