Wƌğ^ƚăƌƚƶɖśğđŭ>ŝɛƚ;^,žŷdeͿ, Pre startup check list (shc ondemand – ClimaCool SHC onDEMAND 30, 50, 70, 85 Manual User Manual
Page 26

www.climacoolcorp.com
24
PreStartUp R-410A SHC onDEMAND
®
10.22.2013
Project Name: _________________________________________________Date:___________________
Address: _____________________________________________________________________________
YES
NO
1. Are modules connected properly per Codes and Installation Manual?
___
___
(Installation, Operation & Maintenance Manual is available at
www.climacoolcorp.com
)
2. Does the module(s) nameplate voltage agree with the site voltage being supplied?
___
___
3. Is there a minimum of 60 mesh strainer on condenser and evaporator inlet water?
___
___
(Fill water to chiller being sure to pass through a minimum of 60 mesh strainer.)
4. Is condenser water system filled and flushed? (See “Filling the Water System” in ClimaCool IO&M.)
___
___
5. Is chilled water system filled, flushed and all air purged from system?
___
___
(Air must be purged from system prior to startup. See “Filling the Water System” in ClimaCool IO&M.)
6. Are all pumps tested and operational?
___
___
7. Is required GPM (verified by pressure differential) supplied to the chilled water side?
___
___
(See project specifications or selection and performance sheets available from ClimaCool Sales Rep.)
8. Is required GPM/Pressure differential being supplied to the condenser?
___
___
(See project specifications or selection and performance sheets available from ClimaCool Sales Rep.)
9. Are the pressure differential flow sensors or switches set to trip on the drop below required flows?
___
___
(Set to trip on low flow (less than 75% flow), not pump on/off.)
10. Have all chiller coupling connections been leak tested?
___
___
11. Is water presently circulating through chiller?
___
___
12. Verified that temperature sensors and voltage/phase monitor have been installed?
___
___
13. Verified power supply agrees with chiller nameplate?
___
___
14. Is power and communication wiring complete to each module?
___
___
15. Verify that wiring and devices meet with approved electrical submittal drawings?
___
___
16. Is required load available to run multiple compressors at startup?
___
___
17. Is control functional to maintain condenser water temperature?
___
___
(Includes maintaining “minimum” inlet temperature; see “Operational Limitations” in ClimaCool IO&M.)
18. Is a water header bypass installed at the chiller? _________ ClimaCool provided? _________Field provided? (Check one)
If you checked “No” to any question above, provide the line reference number and the date of scheduled completion below.
Please note all conditions must be complete prior to the startup date.
______________________________________________________________________________________________________________
______________________________________________________________________________________________________________
This form must be completed and submitted to ClimaCool Corp. a minimum of three (3) weeks prior to final scheduling of any startup.
NOTE: If any of the above items are not complete at time of startup, back charges will be assessed for additional costs.
Contractor
Name:
___________________________
Address: ___________________________
_______________________________________________
___________________________
(Authorized Signature)
Phone:
___________________________
Date: _________________________________________
Pre Startup Check List (SHC onDEMAND
®
)
ͲŵĂŝů
ƚĞĐŚŶŝĐĂůƐƵƉƉŽƌƚΛĐůŝŵĂĐŽŽůĐŽƌƉ͘ĐŽŵ
&ĂdžϰϬϱͲϴϭϱͲϯϬϱϮ
WƌĞ^ƚĂƌƚƵƉŚĞĐŬ>ŝƐƚ;^,ŽŶDEͿ