Electronic positioner (option), 1 technical data, 2 setting – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual
Page 37: Command signal 37,39,40, Pause time 37,51, Positioner 37, Running time 37,51
21.
Electronic positioner (option)
21.1 Technical data
21.2 Setting
The positioner in the actuator controls AUMA MATIC is programmed
according to the purchase order details and is set together with the actuator prior to
delivery.
Due to peculiarities of the regulating system not known beforehand, a readjustment
may become necessary. Before adjusting the positioner, the programming of the
positioner should be checked.
.
Check programming of the logic board according to subclause 20.2.
The self-retaining REMOTE function (see table 4) must be switched
off in conjunction with the positioner.
.
Take off cover plate (figure AE) and carry out required programming at positioner
board (figure AF) according to tables 6 and 7.
37
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructions
with actuator controls AUMA MATIC AM 01.1 / AM 02.1
Command signal (input signal E1, set value)
0/4 – 20 mA (option: 0 – 5 V)
Feedback (input signal E2, actual value)
0 – 5 V (option: 0/4 – 20 mA)
Sensitivity (dead band)
Δ
E (P9)
0.5 % – 2.5 %
Fine tuning “Sens” (P7)
(useful for output speeds < 16 rpm only;
not possible with 1-phase AC motors)
min. 0.25 %
Pause time “t-off ”(P10)
0.5 – 10 s
Input resistance
250 Ohm
Modulating duty with stepping mode
(not required for modulating setting)
:
Running time “t-on” (P8)
effective until error is
≤
25 %; then set value is
automatically reduced by 3.
0.5 – 15 s
Table 5: Technical data for positioner