Electronic positioner (option)

21.1 Technical data

21.2 Setting

The positioner in the actuator controls AUMA MATIC is programmed
according to the purchase order details and is set together with the actuator prior to
delivery.
Due to peculiarities of the regulating system not known beforehand, a readjustment
may become necessary. Before adjusting the positioner, the programming of the
positioner should be checked.

.

Check programming of the logic board according to subclause 20.2.

The self-retaining REMOTE function (see table 4) must be switched
off in conjunction with the positioner.

.

Take off cover plate (figure AE) and carry out required programming at positioner
board (figure AF) according to tables 6 and 7.

37

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Command signal (input signal E1, set value)

0/4 – 20 mA (option: 0 – 5 V)

Feedback (input signal E2, actual value)

0 – 5 V (option: 0/4 – 20 mA)

Sensitivity (dead band)

Δ

E (P9)

0.5 % – 2.5 %

Fine tuning “Sens” (P7)
(useful for output speeds < 16 rpm only;
not possible with 1-phase AC motors)

min. 0.25 %

Pause time “t-off ”(P10)

0.5 – 10 s

Input resistance

250 Ohm

Modulating duty with stepping mode

(not required for modulating setting)

:

Running time “t-on” (P8)
effective until error is

25 %; then set value is

automatically reduced by 3.

0.5 – 15 s

Table 5: Technical data for positioner