Transport, storage and packaging, 1 transport, 2 storage – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual
Page 10: Corrosion protection 10,56, Packaging 10, Storage 10, Transport 10

5.
Transport, storage and packaging
5.1
Transport
.
For transport to place of installation, use sturdy packaging.
.
Do not attach ropes or hooks to the handwheel for the purpose of lifting by
hoist.
.
If multi-turn actuator is mounted on valve, attach ropes or hooks for the pur-
pose of lifting by hoist to valve and not to multi-turn actuator.
Fitting the handwheel:
For transport purposes, handwheels from a diameter of 400 mm are supplied
separately.
Engage manual operation prior to mounting the handwheel! If
the manual operation is not engaged, damage can occur at the
change-over mechanism.
.
Engage manual operation (figure B-1):
Manually lift the red change-over lever while slightly turning the shaft back and
forth until manual operation engages. The manual operation is correctly
engaged if the change-over lever can be lifted by approx. 85°.
Manual force is sufficient for operating the change-over lever. It
is not necessary to use an extension. Excessive force may
damage the change-over mechanism.
.
Install handwheel over the red change-over lever on to the shaft (figure B-1).
.
Release change-over lever (should snap back into initial position by spring
action, figure B), if necessary, push it back manually.
.
Secure handwheel using the snapring supplied.
5.2
Storage
.
Store in well-ventilated, dry room.
.
Protect against floor dampness by storage on a shelf or on a wooden pallet.
.
Cover to protect against dust and dirt.
.
Apply suitable corrosion protection agent to uncoated surfaces.
If multi-turn actuators are to be stored for a long time (more than 6 months), the
following points must be observed additionally:
.
Prior to storage: Protect uncoated surfaces, in particular the output drive parts
and mounting surface, with long-term corrosion protection agent.
.
Check for corrosion approximately every 6 months. If first signs of corrosion
show, apply new corrosion protection.
After mounting, connect actuator immediately to electrical
system, so that the heater prevents condensation.
10
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1
Operation instructions
85°
Figure B-1
Figure B-2