17.1 Setting 2-wire system 4 – 20 mA and 3- /4-wire system 0 – 20 mA
.
Connect voltage to electronic position transmitter via AM.
.
Move valve to
end position CLOSED
.
.
Connect ammeter for 0 – 20 mA to measuring points (figure Y-1).
The circuit (external load) must be connected
(observe max. load R
B
), or the appropriate poles at the terminals
(refer to wiring diagram) must be linked, otherwise no value can
be measured.
.
Turn potentiometer (E2) clockwise to the stop.
.
Turn potentiometer (E2) back a little.
.
Turn potentiometer “0” clockwise until output current starts to increase.
.
Turn potentiometer “0” back until the following value is reached:
for 3- or 4-wire system:
approx. 0.1 mA
for 2-wire system:
approx. 4.1 mA.
This ensures that the signal remains above the dead and live zero point.
.
Move valve to end position OPEN.
.
Set potentiometer “max.” to end value 20 mA.
.
Approach end position CLOSED again and check minimum value
(0.1 mA or 4.1 mA). If necessary, correct the setting.
If the maximum value cannot be reached, the selection of the
reduction gearing must be checked.
31
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructions
with actuator controls AUMA MATIC AM 01.1 / AM 02.1
Figure Y-1
“0” (0/4 mA)
“max.” (20 mA)
Meas.point (+)
0/4 – 20 mA
Meas.point (–)
0/4 – 20 mA
Cover plate
E2