6 led, 5 cordex rectifier cxrf 48-300w, 1 led rectifier status indicator – Alpha Technologies Cordex CXCRF 48-300W User Manual
Page 17: 2 54v dc auxiliary output, Cordex rectifier cxrf 48-300w
0300072-J0 RevA
Page 13 of 46
2.6.4.6 LED
When the green LED is on, the LVD is active (closed).
When the LED is off, the LVD is not active (open).
2.6.5 Cordex Rectifier CXRF 48-300W
Figure 9 : Cordex Rectfier
2.6.5.1 LED
R
ECTIFIER
S
TATUS
I
NDICATOR
The LED indicates the status of the rectifier:
•
Green LED
Normal conditions
•
Orange LED
Stand-by (remote on/off)
•
Red LED
Low output voltage
•
Red blinking LED
Failure (mains, temperature, output short circuit)
2.6.5.2 54V
DC
A
UXILIARY
O
UTPUT
This auxiliary 54V output allows the user to start with a basic bulk shelf without any controller or distribution unit.
Thanks to the modular architecture the user can upgrade the system when the application requires battery back-
up, system monitoring or redundancy. The output power is limited to 300W.
Auxiliary Output
GND
+
-
•
Maximum conductor cross section: 2.0 mm² stranded (14AWG), maximum 8A current
•
The auxiliary output connector on the front is a 3-pole Phoenix contact MC 1,5/ 3-GF-3,81.
The mating connector must be a 3.81mm (0.150”) pitch, 3 positions. It can be ordered from Alpha Technologies.