How the CFR Sends Alarms
To send an alarm, the CFR sends the dial command to the modem and waits up to 60 seconds
for a “connect.” If this fails, it will try the same dial command two minutes later if the modem
responds back to the CFR with a “No Carrier,” “No Dial Tone” or “Busy” messages.
If the modem does not respond (it is disconnected, not powered or is inoperable), the CFR tries
to initalize the modem. It then sends a dial command every two minutes until it is successful. A
successful command is when the modem replies with a “connect” message in less than 60
seconds.
The CFR stores alarm messages in a buffer that holds up to 7 messages. When the modem is
operating, it sends the alarms out in the order they occurred. If the buffer is full, the oldest mes-
sage is discarded and the newest added.
After sending the alarms, the CFR sends a escape command (+++) followed by the hang com-
mand (ATH) to the modem to end the session.
Modem Setup and Control: Sub Menu #52
For most functions you will be asked for a password. The factory set password is 1111. If you
change it, make sure you keep it in a safe and accessible place.