Connecting the external battery pack, 4 connecting the external battery packs, How to connect the external battery packs (sec – Alpha Technologies CFR 3000, CFR 3000RM User Manual
Page 24: Tion 2.4), Mount an alpha external battery pack (section 2.4), 4 connecting the external battery pack
2
Installation
18
2.4
Connecting the External Battery Pack
CAUTION:
1) Verify the pack’s polarity and voltage at the connector before attaching the cable to
the unit.
2) When a pack or batteries have been in storage for more than 6 months, they should
be recharged for at least 24 hours and then thoroughly tested with a load before installa-
tion. If after charging, a battery’s voltage varies more than 0.3 VDC from the others, do
not use it.
Tools and Materials Required:
• DC voltmeter.
• Phillips screwdriver.
Procedure:
1
Verify the battery circuit breaker is switched off. Keep it off until after the unit has been
started with line power.
Loosen the cover plate and slide it up to expose the connector (Figures 2.5, 2.6).
3
Verify the correct DC voltage and polarity at the battery pack’s connector. It should be
between 48 to 53 VDC.
TIP: Wrong voltages or polarities could damage the unit or the battery pack.
4
Connect the pack’s ground wire to the unit’s ground connection.
5
Connect the pack’s connector to the unit’s battery connector.
Battery Pack Connection Finished