beautypg.com

8 transformer output load sharing (continued), Measuring the output current, 2installation 24 – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 30

background image

2

Installation

24

2.8

Transformer Output Load Sharing (Continued)

2.8.2.1: Measuring the Output Current

This uses a clip-on current probe (Figure 2.12 for 240 VAC, Figure 2.13 for 208 VAC and Fig-
ure 2.14 for 230 VAC).

For 120/208/240 VAC units the total current drawn from Winding 1 is the sum of the currents A,
B and C where:

A is the total current drawn by all of the 120V loads connected to the receptacle.

B is the total current drawn by all of the 240V loads connected to the receptacle.

C is the total current drawn from the L1 side of the terminal block.

The total of these currents must not exceed the rated output current for the L1 winding.

For the L2 winding of the transformer, measure the currents at points B and D where:

B is the total current drawn by all of the 240V loads connected to the receptacle.

D is the total current drawn from the L2 side of the terminal block.

The total of these currents must not exceed the rated output current for the L2 winding.

Output

Terminal Block

L2

L1

N

Winding 2

Winding 1

240 VAC

120

VAC

120

VAC

D

C

120 VAC
Receptacle

A

240 VAC

Receptacle

B

Output Current 2

Output Current 1

Output Current L1

Figure 2.12

120/120/240 VAC Current Measurement Points

Output

Terminal Block

L2

L1

N

Winding 2

Winding 1

208 VAC

Not Used

120

VAC

D

C

120 VAC
Receptacle

A

208 VAC

Receptacle

B

Output Current 2

Output Current 1

Output Current L1

Figure 2.13

120/208 VAC Current Measurement Points