beautypg.com

Connecting the rs-232 port, 7 connecting the rs–232 port, Rs-232 connector – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 27: This db–9 port is the rs–232 connection, Section 2.6), How to connect the rs–232 communications port, 6 connecting the rs–232 port, Connecting units with an sid display panel, Connecting units with an iid display panel, 21 2 installation

background image

21

2

Installation

2.6

Connecting the RS–232 Port

The unit can be remotely setup, monitored, and tested by connecting the unit’s DB–9 connector
to a computer’s serial port (Figure 2.8) or communication via a LAN with an optional SNMP
agent. Windows HyperTerminal or any other terminal emulation program is used to communi-
cate with the unit. Section 4 gives more information.

The DB–9 port is a standard feature, but its configuration is different depending upon if a SID or
IID display panel is installed on the unit.

TIPS:
1)
The cable must be less than 50 ft (15m). long and it must be shielded to meet EMI
requirements.

2) The RS–232 is not isolated. Signal ground is directly connected to the internal logic
ground. Contact Alpha if the external battery connector must be referenced to positive
ground instead of negative ground (the factory default).

Connecting Units With an SID Display Panel:

• It uses a basic 3–wire line with software handshaking (XON / XOFF).

• Figure 2.8 shows how to connect the RS–232 port to a standard PC serial port.

• The parameters are: 1200 baud, 8 data bits, no parity, 1 stop bit.

Connecting Units With an IID Display Panel:

• The IID RS–232 port uses a nonstandard cable with RTS/CTS signal straight through

and RX/TX signals reversed.

• The baud rate is operator-configurable.

• For further information on IID RS–232 applications refer to “Information Management

Using the Intelligent Interface Device” manual (Alpha P/N # 018–029–B0–001).

Figure 2.8

RS–232 Wiring Diagrams

1

2

6

7

8

9

3

4

5

CTS

RTS

TXD

RXD

GND

FOR USE WITH IID

EQUIPPED UNITS

1

TXD 2

RXD 3

4

GND 5

6

RTS 7

CTS 8

9

2 RXD

3 TXD

4

5 GND

6

7 RTS

8 CTS

9

1

UNIT RS-232

SERIAL CONNECTOR

(9-PIN FEMALE)

9-PIN IBM PC

SERIAL PORT

1

TXD 2

RXD 3

4

GND 5

6

RTS 7

CTS 8

9

2 TXD

3 RXD

4 RTS

5 CTS

6

7 GND

24

25

1

UNIT RS-232

SERIAL CONNECTOR

(9-PIN FEMALE)

25-PIN IBM PC

SERIAL PORT