Step 1: Enable the CFR’s Modem Feature

The CFR is shipped with the modem feature disabled. To enable it:

1

Connect a computer to the CFR’s RS–232 port (Sections 2.6, 4.1).

2

Go to Menu Item #52 (Figure 4.19). For explanations of each item see “Modem

Setup and Control: Sub Menu #52” in this section.

4.7 Installing and Using the External Modem (Continued)

3

To enable the Automatic Alarm notification, change the following:

i Make sure “Unsolicited Alarms” (Item #509) is disabled (blank instead of “active”).

ii Set the monitoring station’s phone number in Items # 524 “Dial 1” or #525 “Dial 2”

iii If you are not using a US Robotics Sportster, set “Custom Init cmd” (Item #527) to

the values your modem uses (Step 2: Connect and Configure the Modem, #3).

iv If you have more than one unit, set the “Location ID” (Item #526) to a unique, de-

scriptive string (e.g. Rm 222).

4

Set “Enable Automatic Alarms” (Item # 520) to YES.

5

If you want remote dial-in access to the RS–232 menus, set “Enable Remote Ac-

cess” (Item #521) to YES.

External Modem Setup

520 Enable Automatic Alarms (No)
521 Enable Remote Access (No)
522 Set Alarm Actions (11111111)
523 Set Inverter Alarm Delay (0)
524 Set Dial 1 Phone Number (ATDT 234-5678)
525 Set Dial 2 Phone Number (ATDT 234-5678)
526 Set Location ID (CFR UPS in Rm 123)
527 Set Custom init cmd (ATDT X4Q0V1&H0&R1&I0&B1)
528 Set Remote Hang up Time (2)
Last Modem Response (N: )

Figure 4.19

External Modem Setup Screen (Showing Default Values)