Installation sequence – Franklin Fueling Systems TSP-UHS User Manual
Page 2

2
Installation Sequence:
1. Install Conduit, EYS fittings, and Weatherproof
Junction Box.
Mechanical installation
Electrical shock hazards: ensure all
power going to the ATG console is
turned off, tagged, and locked-out
at the power panel before doing any
maintenance or installation work at the
ATG console
2. Pull the sensor cable through the cord grip fitting
at the Junction Box and tighten all remaining cord-
grip fittings. Trim wire/cables to a 6 or 8 inch (15
or 20 cm) service-loop, and splice the sensor and
console cable/wires together.
3. Power up Console for next step
4. Test sensor (verify that an alarm is produced at
ATG console), if it does produce an alarm, seal
EYS seal fittings and electrical connectors with
epoxy – Electrical installation
5. Turn Off Power again if other devices are to be
installed.
6. Reinstall all safety covers and guards, junction box
gasket and covers. Use pipe-dope to seal all fitting
threads.
7. Record the location where the sensor was
installed.
8. Turn On Power and Program the ATG. Refer
to all sections relating to sensors in the Setup/
Programming Guide manual: Service Technician
setup.
General Installation
It is the installer’s responsibility to
comply with all applicable federal, state
and local codes. Failure to do so may
create an Environmental Hazard.
Plan your conduit routing. Dig trenches as necessary
to install conduit from each manhole junction box to the
Intrinsically Safe (I.S.) knockouts at the ATG console. A
junction box inside of the building as a pull box to combine
several sensor cables. If this is done, then only one I.S.
conduit knockout will be used.
If installing in a Phil-Tite double-wall dispenser sump, refer
to Franklin Fueling Systems instructions 602019026.
Conduits must have EYS seal fittings
installed in accordance with NFPA
70 (National Electric Code) and NFPA
30A (Automotive and Marine Service
Station Code). Failure to seal conduits
in accordance with NFPA 30A, and
NFPA 70 could allow flammable vapors
to travel through the conduit in the
ATG console. An explosion could result
causing serious injury, property loss,
or death.
You must install a weatherproof, electrical junction
box inside each manhole. The junction box should be
installed high on the manhole wall to prevent it from being
submerged during heavy rains.
2 wires/cable from console
2-conductor cable from sensor
J-box
From 2-wire sensor
SE
NS
OR
N
IN(WHT)
Only remove the
jumper link between:
in (wht) & gnd (blk),
when a sensor
channel is wired
Note: The
PWR (red)
terminal is
not used with
2-wire sensors
GND(BLK)
PWR(RED)
PWR(RED)
SE
NS
OR
1
IN(WHT)
GND(BLK)
Insert the unstripped wires fully
into the self-sealing, no-strip
electrical connector.
Use slip-joint pliers and seat
the black portion to make a
good electrical connection
IN
(WHT)
GND
(BLK)
Figure 2: Splice Connection
Seal all threaded fittings and conduit threads to produce a
weatherproof seal during installation/maintenance.
Electrical Wiring
The two-wire TSP-UHS sensor does not have a red
(power) conductor, therefore, if there is a PWR (RED)
interface terminal at the console, it is not used. When a
3-conductor Alpha cable is used, the red conductor can be
clipped or taped back on both ends.