beautypg.com

Electrical wiring – Franklin Fueling Systems TSP-HLS User Manual

Page 3

background image

7. Test sensor (rotate float end up to verify that an

alarm is produced at ATG console). If the sensor

does produce an alarm, seal EYS seal fittings

with epoxy.

8. Turn power off again if other devices are to be

installed (Repeat Step 3)

9. Reinstall all safety covers and guards, junction

box gasket and covers – use pipe-dope to seal all

fitting threads.

10. Adjust the ACTUATION LEVEL (

FLOAT HeigHT)

to

equal the High Level Alarm level for this Tank .

a. Loosen the ⅞ inch swage locknuts
b. Move the shaft to set float height
c. Retighten the swage locknuts to hold position.

11. Install the manhole cover.
12.

Record the location where the sensor was

installed (TANK), and the Float Height = High

Level Alarm

Level on the back page of this

document. This information is needed when

programming the ATG.

13. Turn power on and program the ATG – Refer to

Sensors in the console Setup / Programming &

Installation manuals.

general installation Notes

it is the installer’s responsibility to

comply with all applicable federal, state

and local codes. Failure to do so may

create an environmental Hazard.

Fill the bottom of the manhole with crushed stone to

facilitate drainage. Do not cover the sensor or bung access

hole with fill material, it must remain accessible for sensor

installation and for service / testing.
Plan your conduit routing. Dig trenches as necessary

to install conduit from each manhole junction box to the

Intrinsically Safe (I.S.) knockouts at the ATG console. The

conduit may enter the manhole either from its bottom or

through its side. A junction box inside of the building as a

pull box to combine several sensor cables. If this is done,

then only one I.S. conduit knockout will be used.

Conduits must have EYS seal fittings

installed in accordance with NFPA

70 (National electric Code) and NFPA

30A (Automotive and Marine Service

Station Code). Failure to seal conduits

in accordance with NFPA 30A, and

NFPA 70 could allow flammable vapors

to travel through the conduit in the

ATg console. An explosion could result

causing serious injury, property loss,

or death.

You must install a weatherproof, electrical junction

box inside each manhole. The junction box should be

installed high on the manhole wall to prevent it from being

submerged during heavy rains.

Note: Seal all threaded fittings and conduit fittings to

produce a weatherproof seal.

2 wires/cable from console

2-conductor cable from sensor

J-box

From 2-wire sensor

SE

NS

OR

N

IN(WHT)

Only remove the

jumper link between:

in (wht) & gnd (blk),

when a sensor

channel is wired

Note: The

PWR (red)

terminal is

not used with

2-wire sensors

GND(BLK)

PWR(RED)

PWR(RED)

SE

NS

OR

1

IN(WHT)
GND(BLK)

Insert the unstripped wires fully

into the self-sealing, no-strip

electrical connector.
Use slip-joint pliers and seat

the black portion to make a

good electrical connection

IN

(WHT)

GND

(BLK)

Figure 3: Sensor Wiring

electrical Wiring

Reference the ATG Installation Manual and see

Figure 3

(above) for TSP‑HLS sensor wiring details. The two‑wire

TSP‑HLS sensor does not have a red (power) conductor,

therefore, the PWR (RED) interface terminal at the console

is not used. If a 3-conductor Alpha cable is used, the red

conductor can be clipped or taped back on both ends.

Caution

Warning

Caution

Warning

3