Technical bulletin, Detect mode troubleshooting – Franklin Fueling Systems TS-LS300 Troubleshooting Tips for the LS300 Line Leak Detection System User Manual
Page 2

TECHNICAL BULLETIN
TB0505-01
May 09, 2005
Franklin Fueling Systems • 3760 Marsh Rd. • Madison WI 53718 USA
Tel: +1 608 838 8786 • 800 225 9787 • Fax: +1 608 838 6433 • www.franklinfueling.com
Detect Mode Troubleshooting
Condition
Definition
Potential Causes
Proposed Action
Leak Alarm
• Gross (3gph) Leak
Alarm
The LS300 has detected
a pressure loss
consistent with a leak of
3gph or greater.
• Monthly or Annual
Precision Test Failed
The LS300 has detected
a pressure loss
consistent with a .2gph
leak (one flash) or a
.1gph leak (two flashes).
• Leak in the pipeline
• Submersible pump check
valve not seating properly
• Leak in the manual
pressure relief (FE Petro
Pump)
• Adjustable Functional
Element not seating
properly/defective. (Red
Jacket)
• Push the Test/Reset button to clear alarm.
Conduct a manual leak test to confirm the line
status. If the LS300 again detects a leak after
three failed test sessions, shut down the line and
troubleshoot the pressure loss.
• Check valve seating area should be clean and free
of debris. Clean area if necessary.
• Verify that the manual pressure relief screw (FE
Petro) is turned clockwise.
• Check sump areas for signs of leakage.
• For further information, see FE Petro Service
Bulletin SB007 STP/IST Static Pressure Testing.
Transducer Not Seen
The LS300 cannot
detect the signal coming
from the transducer
• Transducer is wired
incorrectly
• Wiring or connections to the
transducer are loose or
broken
• Transducer is defective
• See the LS300 Auto-Learn User’s Guide‘s
Transducer Troubleshooting section for specific
troubleshooting information.
Pipeline Failed to Hold
Pressure
After the submersible
pump shut off, pipeline
pressure dropped
immediately to 0 psi.
• Large leak in the pipeline
• Check valve removed or
stuck open
• Press Test/Reset button to clear alarm. Conduct a
manual 3gph test and confirm line status.
• Verify that the check valve is installed in the
submersible pump and is seating properly.
• Check sump areas for signs of leakage.
• For further information, see FE Petro Service
Bulletin SB007 STP/IST Static Pressure Testing.
Insufficient Pressure to
Conduct Test
Pipeline is not fully
pressurizing when the
submersible pump is
turned on.
• Power to submersible is
OFF
• Leak in the pipeline
• Transducer problem
• Verify that there is power to the submersible
pump.
• Check sump areas for signs of a large leak.
• See the LS300 Auto-Learn User’s Guide‘s
Transducer Troubleshooting section for specific
troubleshooting information.
Calibration is Incomplete
The line will not detect
leaks because the line is
not Learned
• Learn sequence was not
attempted or was not
completed properly
• See the LS300 Auto-Learn User’s Guide‘s Line
Calibration. Follow the instructions on learning a
line.
Highly flammable vapors or liquids may be present in the environment in which this equipment is
installed or serviced. Installing or working on this equipment means working in an environment that
presents risks of severe injury or death if instructions and standard industry practices are not followed.
Follow all applicable codes governing the installation and servicing of this product and the entire system.
Always lock out and tag electrical circuit breakers while installing or servicing this equipment and related
equipment. Refer to the Installation and Owner’s Manual of this equipment and related equipment for
complete installation and safety information.
Warning