Mag sensor register set, Relay data – Franklin Fueling Systems TS-5000 evo MODBUS Installation & Setup User Manual

Page 14

background image

14

Mag Sensor Register Set

Mag Sensors Start Address = (SensorNumber-1)*7+5200

Register Description

Address Offset

Data Format

Product Level

0,1

Signed Integer (See Length Units)

Water Level

2,3

Signed Integer (See Length Units)

Status Register

4

See Mag Sensor Status Register

Reserved

5-8

Mag Sensor Status Register

Bit #

Status Bit

0

Water Warning Active 

1

Water Alarm Active

2

Product Alarm Active

3

Installation Alarm Active

4

Sensor Missing Alarm Active

5

Sensor Sync Alarm Active

6

Sensor Float Missing Active

7-15

Reserved

Relay Data

Relay Status Register

PS Relay Start Address = (PSRelay-1)*2+5900
Relay Start Address = (Relay-1)*2+6000

Bit #

Status Bit

0

Relay Status 

1-15

Reserved

Relay Status State Table

Bit Value

Relay State

0

Deactivated

1

Active