beautypg.com

Tank data – Franklin Fueling Systems TS-5000 evo MODBUS Installation & Setup User Manual

Page 11

background image

11

Volume Units Table

Register Value

Unit Type

Units Precision

0

Liters

0.1 L

1

Gallons

0.1 gal

2

Imperial Gallons

0.1 imp gal

Temperature Units Table

Register Value

Unit Type

Units Precision

0

Centigrade

0.1 C

1

Fahrenheit

0.1 F

Density Units Table

Register Value

Unit Type

Units Precision

0

Kilograms per cubic meter

0.1 kg/m^3

1

Grams per cubic centimeter

1 g/cm^3

2

Pounds per cubic foot

0.001 lbs/ft^3

Mass Units Table

Register Value

Unit Type

Units Precision

0

Kilograms

0.1 kg

1

Grams

1 g

2

Pounds

0.01 lbs

Tank Data

Tank Data Register Set

Tank Register Start Address = (TankNumber-1)*36+200

Register Description

Address Offset

Data Format

Resolution

Tank Status Register

0, 1

See Tank Status Register

Tank Alarms Register*

2,3

See Tank Alarms Register

Product Level

4,5

Signed 32-bit Integer

See Length Units

Water Level

6,7

Signed 32-bit Integer

See Length Units

Temperature

8,9

Signed 32-bit Integer

See Volume Units

Gross Product Volume

10,11

Signed 32-bit Integer

See Volume Units

Net Product Volume

12,13

Signed 32-bit Integer

See Volume Units

Water Volume

14,15

Signed 32-bit Integer

See Volume Units

Ullage Volume

16,17

Signed 32-bit Integer

See Volume Units

Density

18,19

Signed 32-bit Integer

See Density Units

Net Density

20,21

Signed 32-bit Integer

See Density Units

Mass

22,23

Signed 32-bit Integer

See Mass Units

Reserved

24-31

N/A

*Note that this register does not contain all possible alarms for a tank.
Tank Status Register

Bit #

Status Bit

0

Tank in Alarm 

1

Delivery in Progress

2

Static Tank Test in Progress

3-31

Reserved

This manual is related to the following products: